INSTALLATION INSTRUCTIONS
Pump Start Relay Connection (Water supply by pump system)
This controller does not provide mains power to drive a pump. A pump must be driven
via an external relay and contactor setup as detailed below. The controller provides
a low voltage signal that actuates the relay which in turn enables the contactor and
î‚¿nally the pump.
HINT: Although the controller has permanent memory and thus a default program
will not cause erroneous valve actuation as in some controllers, it is still good
practice when using a system where the water supply comes from a pump to
connect unused stations on the unit back to the last used station. This in effect,
inhibits the chances of the pump ever running against a closed head.
Single Phase Pump Installation
COM
COM COM
SENS PUMP 1 ST1 ST2 ST3 ST4 ST5 ST6
PUMP 2
Link any unused
stations to the
last active station.
Note: It is recommended to always use a relay between the controller and the pump
starter.