User manual

3 Description
D
igital panel meter for displaying measured values, as well as monitoring limit values in industrial
a
pplications.
6-digit 14-segment LED display, 14 mm, for displaying measured values and dialogs
Running text can be switched on as Help Text
L
anguage for the Help Text selectable as English or German
Signal input for strain gauges 3.3 mV/V, 3.0 mV/V, 2.0 mV/V, 1.5 mV/V and 1.0 mV/V
Sampling rate 10 readings per second
Digital filter (1st order) for smoothing display fluctuations with unstable input signals
Customised linearisation
MIN/MAX memory function
Manually-controlled Totaliser function
2 Relay outputs (changeover contacts) for limit monitoring
Start delay for relay outputs after Power ON
Versions for supply voltage 10 ... 30 V DC and 100 … 240 V AC ± 10%
Excitation supply 10 V DC / 30 mA for powering 350 bridges
Additional aux. power output 24 V / 30 mA with AC supply
Programmable via the front keys
Multifunction key and two multifunction inputs, function programmable
4 Display/Operating elements
(1) Display
- 14 segment display, 6-digit, red
- Height of figures 14 mm
(2) Status display, 2 LED annunciators , red
- Switching status of Alarm 1 and Alarm 2
- Indication Function Group or Function
(3) MP-Key and Programming Keys
- Multifunction key (MP-Key)
- Return from Function Group
- Return from Function
- Select previous Function Group
- Select previous Function
- Decrement parameter value
- Select next Function Group
- Select next Function
- Increment parameter value
- Enter a Function Group
- Enter a Function
- Accept the new setting
(4) Space for unit overlay
To enter the Programming Menu
+ > 3 sec
To display Device Type and Software Version
+ + > 5 sec
To restore factory default settings
+ > 3 sec
e
n
g
l
i
s
h
Page 5