Installation Guide
R38 End Feed
(For Electrical Feed Away From Junction Box)
Makes electrical connection from BX, Romex or Greenfield. Use at
end of Trac run when wiring from above.
1. Make sure power is OFF.
2. Remove connector cover.
3. Attach 1/2’’ connector (not supplied) and secure to BX,
Romex or Greenfield.
4. Insert End Feed connector fully into Trac section with polarity
arrow pointing toward Trac polarity line, secure with set screw.
5. Attach Trac to ceiling following instructions supplied with the
Trac section.
6. Fasten positive wire to screw terminal marked “P”.
7. Fasten neutral wire to screw terminal marked “N”.
8. Replace cover and secure with screw.
1/2" Connector
(not supplied)
Feed Connector
Terminal
Screws
Set
Screw
Polarity
Arrow
Polarity
Line
Cover
Ground
Screw
Cover Screw
R38 End Feed
Existing Junction Box
(not supplied)
Terminal Screws
Cover
Mounting Plate
Set
Screw
Screws
Knockout
Polarity
LIne
Polarity
Arrow
Feed Connector
Cover Screw
R36 T-Bar End Feed
Polarity Line
Polarity Arrow
Set Screw
Optional ON/OFF
Switch
Feed Connector
R22 Cord & Plug Set
Makes electrical connection from standard AC wall receptacle.
1. Make sure power is OFF.
2. Insert feed connector fully into Trac section with polarity arrow
pointing toward Trac polarity line, secure with set screw.
3. Attach Trac to ceiling following instructions supplied with the
Trac section.
4. Install ON/OFF switch following instructions enclosed with
switch if desired.
5. Use adhesive tabs to secure cord to ceiling and/or wall surface.
6. Plug into wall receptacle.
R36 T-BAR End Feed
(for use only with junction box)
Makes electrical connection at standard Junction Box placed
above dropped ceiling.
1. Make sure power is OFF.
2. Remove connector cover.
3. Remove knockout as needed.
4. Insert T-Bar End Feed connector fully into Trac section with
polarity arrow pointing toward Trac polarity line, secure with
set screw.
5. Attach Trac to ceiling following instructions supplied with the
Trac section.
6. Pull junction box wires through knockout.
7. Attach mounting plate to junction box.
8. Fasten positive wire to screw terminal marked “P”.
9. Fasten neutral wire to screw terminal marked “N”.
10. Replace cover and secure with screw.
R22 Cord & Plug Set
For Juno R Series Trac Connectors, Electrical Feeds and Accessories
INSTALLATION INSTRUCTIONS
WARRANTY
Limited warranty located at:
www.acuitybrands.com/customerresources/terms_and_conditions.aspx
4 of 4
1300 S. Wolf Road • Des Plaines, IL 60018 • Phone 800-323-5068 • Visit us at www.acuitybrands.com/juno-trac
©2017 Acuity Brands Lighting, Inc. Rev 3/17 P3069
Technical Services Phone (888) 387-2212