Installation Instructions

DHW heating
6 720 645 817 (2010/09)
68
Specification
T
Sp
Cylinder temperature
T
Z
DHW outlet temperature
Cylinder type Unit SK 300-3 ZB SK 400-3 ZB SK 500-3 ZB SK 800 ZB SK 1000-ZB
Heat exchanger
Heat transfer Indirect coil Indirect coil Indirect coil Indirect coil Indirect coil
Number of coils 10 13 17 32 32
Available capacity l 293 388 470 760 950
Heating water content l 10 12 14 36.1 42.1
Heating surface m
2
1.5 1.8 2.6 5.7 6.7
Performance factor N
L
1)
to
DIN 4708 at max. output
1) The performance factor N
L
corresponds to the number of residential units to be supplied, each with 3.5 occupants, one standard
bath tub and two further draw-off points.
8.7 13.5 17 35 45
Further details
Available amount of DHW
(without reheating)
2)
T
Sp
= 60 °C
and
- T
Z
= 45 °C
- T
Z
= 40 °C
2) Distribution losses outside the cylinder have not been taken into account.
l
l
365
426
482
563
584
682
1010
1178
1262
1473
Standby loss (24 h) to
DIN 4753 part 8
2)
kWh/d 2.2 2.5 3.1 4.6 4.8
Max. operating pressure, water bar 10 10 10 10 10
Max. operating pressure, heating bar 10 10 10
Weight (empty, excl. packaging) kg 135 150 170 310 414
Colour White White White White White
Tab. 38