Installation Instructions

System schemes
6 720 645 817 (2010/09)
14
1.6 System scheme 6: one unmixed heating circuit, two mixed heating circuits, low loss
header
Hydraulic scheme with controller (schematic diagram)
Fig. 6
AF Outside temperature sensor
CUx Boiler control unit
FB 100 Remote control
FW 200 Weather-compensated controller
HP Heating circuit pump (primary circuit)
IPM 1 Load switching module for one heating circuit
IPM 2 Load switching module for two heating circuits
M
2,3
3-way mixer
MF
2,3
Mixer circuit temperature sensor
P
1,3
Heating circuit pump (secondary circuit)
TB Temperature limiter
VF Common flow temperature sensor
1 Module position: on the heat source
3 Module position: on the wall
Heating system components
Suprapur gas condensing boiler for balanced flue
operation
One unmixed heating circuit
Two mixed heating circuits
Weather-compensated controller
Features
Generally, we would recommend the installation of a
low loss header on site to ensure reliable transfer of
the required heating output.
The FW ... weather-compensated controller is
preferred for its higher utilisation of condensing
technology.
Determine the system water content and select a
corresponding expansion vessel (Æ page 39).
Install a mechanical safety limiter (TB 1) in
accordance with the underfloor heating system
manufacturer's instructions.
Install safety assembly to DIN 1988.
Function description
The heating circuits are regulated by an FW 200
weather-compensated controller. This always requires
the IPM 1 and IPM 2 load switching modules. A 2-wire
BUS system enables communication between the boiler
control unit, the controller and the load switching
modules.