Datasheet
WARNING:
Translationfrom Japanese: The attachedpower cable is only for this product.
Do not use the cable for another product.
NOTE: In North America, AC power cords must not exceed 4.5 m
(approximately 14.75 ft) in length, to comply with National Electrical Code
(NEC) Sections 400-8 (NFPA 75, 5-2.2) and 210-52, and Canadian Electrical
Code (CEC) Section 4-010(3). The cords supplied with the router are in
compliance.
Table 20 on page 169 provides specifications and Figure 61 on page 170 depicts the plug
on the AC power cord provided for each country or region.
Table 20: AC Power Cord Specifications
Plug TypeElectrical SpecificationCountry
SAA/3240 VAC, 50 Hz ACAustralia
CEE 7/7220 or 230 VAC, 50 Hz ACEurope (except Italy and United Kingdom)
CEI 23-16230 VAC, 50 Hz ACItaly
NEMA 5-15P120 VAC, 60 Hz ACNorth America
BS89/13240 VAC, 50 Hz ACUnited Kingdom
169Copyright © 2012, Juniper Networks, Inc.
Appendix D: Power Guidelines, Requirements, and Specifications for the M7i Router