M7i Router Environmental Specifications
M7i Router Environmental Specifications on page 165
M7i Router Environmental Specifications
Table 18 on page 165 specifies the environmental conditions required for normal router
operation. In addition, the site should be as dust-free as possible. Dust can clog air intake
vents and filters, reducing cooling system efficiency. Check the filters and vents frequently,
cleaning them as necessary. For more information, see “Routine Maintenance Procedures
for the M7i Router” on page 73.
Table 18: Router Environmental Tolerances
ToleranceDescription
No performance degradation to 10,000 ft (3048 m)Altitude
Normal operation ensured in relative humidity range of 5% to 90%,
noncondensing
Relative humidity
Normal operation ensured in temperature range of 32°F to 104°F
(0°C to 40°C)
Temperature
Tested to meet Telcordia Technologies Zone 4 earthquake
requirements
Seismic
AC: 1400 BTU
DC: 1600 BTU
Thermal output
NOTE: Install the router only in restricted or service areas, such as dedicated
equipment rooms and equipment closets, in accordance with Articles 110-16,
110-17, and 110-18 of the National Electrical Code, ANSI/NFPA 70.
For additional safety guidelines and requirements, see “General Safety
Guidelines for Juniper Networks Devices” on page 129.
Related
Documentation
M7i Router Physical Specifications on page 163