Datasheet
extinguishers displace the oxygen from the point of combustion to eliminate the fire. For
extinguishing fire on or around equipment that draws air from the environment for cooling,
use this type of inert oxygen displacement extinguisher instead of an extinguisher that
leave residues on equipment.
Do not use multipurpose Type ABC chemical fire extinguishers (dry chemical fire
extinguishers) near Juniper Networks devices. The primary ingredient in these fire
extinguishers is monoammonium phosphate, which is very sticky and difficult to clean.
In addition, in minute amounts of moisture, monoammonium phosphate can become
highly corrosive and corrodes most metals.
Any equipment in a room in which a chemical fire extinguisher has been discharged is
subject to premature failure and unreliable operation. The equipment is considered to
be irreparably damaged.
NOTE: To keep warranties effective, do not use a dry chemicalfire extinguisher
to control a fire at or near a Juniper Networks device. If a dry chemical fire
extinguisher is used, the unit is no longer eligible for coverage under a service
agreement.
We recommend that you dispose of any irreparably damaged equipment in an
environmentally responsible manner.
Related
Documentation
General Safety Guidelines for Juniper Networks Devices on page 129•
• General Safety Warnings for Juniper Networks Devices on page 130
• General Electrical Safety Warnings for Juniper Networks Devices on page 148
• DC Power Electrical Safety Warnings for Juniper Networks Devices on page 154
M7i Router Installation Safety Guidelines and Warnings
•
M7i Chassis Lifting Guidelines on page 134
•
Installation Safety Warnings for Juniper Networks Devices on page 135
M7i Chassis Lifting Guidelines
The weight of a fully configured chassis is about 36.5 lb (16.6 kg). Observe the following
guidelines for lifting and moving the router:
•
Before moving the router, read the guidelines in “M7i Router Site Preparation Checklist”
on page 37 to verify that the intended site meets the specified power, environmental,
and clearance requirements.
•
If a lift cannot be used, one person can lift the router. Another person is required install
the mounting screws.
Copyright © 2012, Juniper Networks, Inc.134
M7i Multiservice Edge Router Hardware Guide