Network Router User Manual

Appendix B
Environmental Specifications
Router Environmental Specifications on page 173
Router Environmental Specifications
Table 19 on page 173 specifies the environmental specifications required for normal
router operation. In addition, the site should be as dust-free as possible. Dust can
clog air intake vents, reducing cooling system efficiency. Check the vents frequently,
cleaning them as necessary. For more information, see Maintaining Hardware
Components on page 73.
Table 19: Router Environmental Specifications
ValueDescription
No performance degradation to 10,000 ft (3048 m)Altitude
Normal operation ensured in relative humidity range of 5% to
90%, noncondensing
Relative humidity
Normal operation ensured in temperature range of 32°F (0°C) to
104°F (40°C)
Non-operating storage temperature in shipping crate: 40°F (40°C)
to 158°F (70°C)
Temperature
Designed to meet Telcordia Technologies Zone 4 earthquake
requirements
Seismic
AC: 3276 BTU/hour (960 W)
DC: 1965 BTU/hour (576 W)
Maximum thermal output
NOTE: Install the router only in restricted areas, such as dedicated equipment rooms
and equipment closets, in accordance with Articles 110-16, 110-17, and 110-18 of
the National Electrical Code, ANSI/NFPA 70.
For additional safety guidelines and requirements, see Safety and Regulatory
Compliance Information on page 135.
Router Environmental Specifications 173