Instruction Manual

Pull the control knob off the central plate so that the adjustment rings are vis-
ible Bild.
Pulling off is done by hand or with a suitable tool, e.g. vacuum lifting tool or
key cap puller.
Turn the large blue adjustment ring clockwise to the desired minimum temper-
ature. Each notch corresponds to a change of about 2°C.
Turn the small red adjustment ring anticlockwise to the desired maximum tem-
perature.
The respective adjustment ring can only be turned in one direction. To return
to the original setting, continue turning to the respective position.
Replace the control knob, observing the coding (Fig. 4, bottom) of the control
knob and rotary axle.
8 Technical data
Rated voltage AC 220 ... 240 V ~
Mains frequency 50 / 60 Hz
Switching current 10 A
Connected load
Ohmic load 2300 W
Standby power max. 0.15 W
Ambient temperature -5 ... +45 °C
Storage/transport temperature -25 ... +70 °C
Cable length inputs max. 100 m
Controller class (EU 811/2013) IV
Contribution to energy efficiency 2%
FFNTC remote sensor
Dimensions Ø×H 7.8 × 28 mm
Length connecting cable 4 m (can be extended to 50 m)
Degree of protection IP 67
Remote sensor resistance values
Temperature
(°C)
Resistance
(kΩ)
Temperature
(°C)
Resistance
(kΩ)
5 89.5 30 26.2
10 68.8 35 20.9
15 53.5 40 16.7
20 41.9 45 13.5
25 33.0 50 11.0