Instruction Manual

Activating/deactivating permanent LED operation
In permanent operation, the status LED lights up continuously during the active heat-
ing phase.
Press the control knob for longer than 10 seconds until the LED lights up or
flashes in the colour
magenta
.
LED lights up magenta = permanent operation is active
LED flashes magenta = permanent operation is inactive (default setting)
Press the control knob briefly to switch the mode.
Press the control knob for more than one second to adopt the displayed mode.
After 10 seconds without actuation, the displayed mode is automatically adop-
ted.
7 Information for electrically skilled persons
Remote sensor mounting instructions
The remote sensor must meet the requirements of protection class II and be routed
together with sensor cable S03VV in a protective tube. This protects the remote
sensor from humidity and allows for an easier exchange in the event of repair.
Is the status LED (3) flashes red rapidly, there is an error at the remote
sensor. No temperature measurement, and thus no control, is possible.
If the sensor cable is interrupted or no remote sensor is connected, continuous
heating is carried out. If there is a short circuit of the sensor cable, heating is
not carried out.
DANGER!
Mortal danger of electric shock.
Disconnect the device. Cover up live parts.
Connecting and fitting the device
Recommended installation height: 1.50 m.
Floor thermostat
6 / 10
82404923 29.11.2022