User Manual
5 Technical data
19
Ambient conditions
Output
Supply
Housing
Ambient temperature range 0 to +55°C, with side-by-side mounting: 0 to +40°C
Storage temperature range -40 to +70°C
Climatic conditions ≤ 75% rel. humidity, no condensation
Cleaning and care of the
front panel
The front panel can be cleaned with all the usual cleaning and rinsing agents.
Do not use solvents such as methylated spirit, white spirit, P1 or xylene.
Relay (changeover contact) 150,000 operations at 10A 250V AC resistive load
Supply voltage 230V AC +10/-15%, 48 — 63Hz or 115V AC +10/-15%, 48 — 63Hz
(electrically isolated from measurement input)
12 — 24V DC +15/-15%, 24V AC +15/-15%, 48 — 63Hz
(not electrically isolated from measurement input)
Power consumption < 3VA
Material polycarbonate
Mounting in panel cut-out with bezel seal
Operating position unrestricted
Weight approx. 160 g
Protection front IP65, rear IP20
Flammability class UL 94 VO