User Manual

4 Commissioning the instrument
13
Alarm suppression time
An alarm is not considered to be an alarm for this period. The LED K1
flashes in the display. If an alarm is present for longer than , then it is
considered to be an alarm, the LED K1 lights up and the relay is switched in
accordance with the parameter (see parameter ).
0 ... 60min
Switch-on delay after power-on
For the time-delayed switch-on of the alarm monitoring. No alarms are eval-
uated during this time, only probe errors.
0 ... 60min
Relay type
0: relay operates as a break contact in the event of an alarm
1: relay operates as a make contact in the event of an alarm
0 … 1
Response to over/underrange
0: relay drops out at once
1: relay pulls in at once
0 … 1
Parameter Meaning
Value range
from...factory-set...to