User Manual
6 Technical data
22
Output
Supply
Housing
Cleaning and care of the
front panel
The front panel can be cleaned with all the usual cleaning and rinsing agents.
Do not use solvents such as methylated spirit, white spirit, P1 or xylene.
1 relay (changeover contact)
on Type 701060/XX1-XX
150,000 operations at 10A 250V AC, 50Hz resistive load
2 relays (make contacts)
on Type 701060/XX2-XX
100,000 operations at 5A 250V AC, 50Hz resistive load
Supply voltage 230V AC +10/-15%, 48 — 63Hz or 115V AC +10/-15%, 48 — 63Hz
(electrically isolated from measurement input)
12 — 24V DC +15/-15%, 24V AC +15/-15%, 48 — 63Hz
(not electrically isolated from measurement input)
Power consumption < 3VA
Material polycarbonate
Mounting in panel cut-out with bezel seal
Operating position unrestricted
Weight approx. 160g
Protection front IP65, rear IP20
Flammability class UL 94 VO