6 Technical data
20
6 Technical data
Meas. input Designation Meas. range Meas. accuracy
1
/
ambient tempera-
ture error
Recognition of ...
Probe short-
circuit
Probe break
Resistance
thermometer
Pt100 EN 60 751 -200 to +600°C 0.1%/ 100ppm/°C yes yes
Pt1000 EN 60 751 -200 to +600°C 0.1%/ 100ppm/°C yes yes
KTY2X-6 (PTC) -50 to +150 °C 1%/ 100ppm/°C yes yes
resistance 0 3000 customer table
3
0.1%/ 100ppm/°C
3
= 0 yes
Measuring current with Pt100: 0.2 mA, with Pt1000, KTY2X-6 or resistance: 0.02 mA
Lead compensation is adjustable via the parameter Lead compensation resistance
The total resistance (sensor+lead) must not exceed 320for Pt100 and 3200for Pt1000, KTY2X-6 or resistance.
Thermo-
couple
Fe-Con J EN 60 584 -200 to +999 °C 0.4%/ 100ppm/°C
2
no yes
Fe-Con L DIN 43 710 -200 to +900 °C 0.4%/ 100ppm/°C
2
no yes
NiCr-Ni K EN 60 584 -200 to +999 °C 0.4%/ 100ppm/°C
2
no yes
-10 to 60 mV customer table
3
0.1%/ 100ppm/°C
3
no yes
For the voltage input (-10 to 60 mV), terminal temperature compensation for thermocouples can be used.
Internal terminal temperature compensation can be switched off through the setup program (0°C).