4 Commissioning the instrument
16
Input
Sensor connected in 2-wire circuit
Measurement input group 1 on Type: 701060/X1X-XX
Pt100:
Pt1000:
KTY2X-6:
or
Measurement input group 2 on Type: 701060/X2X-XX Fe-Con J:
Fe-Con L:
NiCr-Ni K:
or
Measurement input group 3 on Type: 701060/X3X-XX 0(4)... 20 mA:
/
Measurement input group 4 on Type: 701060/X4X-XX 0 ... 10 V: /
Start value for indication range with measurement input voltage or current
Example: input signal (e.g. 4 to 20mA) is to be represented in the display
from -10 to 50. Set S.cL= -10 and S.cH=50.
-999 ... 0... +999
End value for indication range with measurement input voltage or current -999 ... 100... +999
Signal for measurement input current: 0 = 0 to 20mA
1 = 4 to 20mA
0, 1
Process value offset
PV offset in °C, °F or digit (no unit)
-99.9 ... 0.0 ... 99.9
Parameter Meaning
Value range
from...factory-set...to