Datasheet

09.04/00440437
Data Sheet 70.1060JUMO GmbH & Co. KG • 36035 Fulda, Germany Page 2/4
Technical data
Additional data
Ambient conditions
Output
Supply
Measurement
input
Designation Measuring range Meas. accuracy
1
/
ambient
temperature error
Recognition of ...
Probe
short-circuit
Probe break
Resistance
thermometer
Pt100 EN 60 751 -200 to +600°C 0.1%/ 100ppm/°C is recognized is recognized
Pt1000 EN 60 751 -200 to +600°C 0.1%/ 100ppm/°C is recognized is recognized
KTY2X-6 (PTC) -50 to +150 °C 1%/ 100ppm/°C is recognized is recognized
Resistance 0 3000 customer table
3
0.1%/ 100ppm/°C
3
= 0 is recognized
Measuring current for Pt100: 0.2 mA, for Pt1000, KTY2X-6 and resistance: 0.02 mA
Lead compensation is adjustable via the parameter Lead compensation resistance
The total resistance (sensor+lead) must not exceed 320for Pt100 and 3200for Pt1000, KTY2X-6 or resistance.
Thermocouple Fe-Con J EN 60 584 -200 to +999 °C 0.4%/ 100ppm/°C
2
- is recognized
Fe-Con L DIN 43 710 -200 to +900 °C 0.4%/ 100ppm/°C
2
- is recognized
NiCr-Ni K EN 60 584 -200 to +999 °C 0.4%/ 100ppm/°C
2
- is recognized
-10 to 60 mV customer table
3
0.1%/ 100ppm/°C
3
- is recognized
For the voltage input (-10 to 60 mV), terminal temperature compensation can be used for thermocouples.
Internal terminal temperature compensation can be switched off via the setup program (0°C).
Current 0 20 mA -2 to 22 mA
scalable with and
or customer table
0.1%/ 100ppm/°C
3
--
4 20 mA 2.4 to 21.6 mA
scalable with and
0.1%/ 100ppm/°C
3
is recognized is recognized
Input resistance R
IN
3
Voltage 0 10 V -1 to 11 V
scalable with and
or customer table
0.1%/ 100ppm/°C - -
Input resistance R
IN
100k
1.) The accuracies refer to the measuring range span.
2.) valid from -50°C
3.) A valid customer table must be entered via the setup program and changed over to in the instrument.
This may reduce the measuring accuracy.
Sampling time 250 msec
Input filter 1st order digital filter; filter constant adjustable from 0.1 99.9sec
Measurement offset adjustable from -99.9 to +99.9 via the parameter
Special features display of temperature unit: °C, °F (Fahrenheit) or switched-off
Customer table The setup program acquires a maximum of 20 value pairs and uses them for the linear interpolation
of 20 new calibration points.
Ambient temperature range 0 to +50°C, with side-by-side mounting: 0 to +40°C
Storage temperature range -40 to +70°C
Climatic conditions 75% rel. humidity, no condensation
Cleaning and care of front panel The front panel can be cleaned with all the usual cleaning and rinsing agents.
Do not use solvents such as methylated spirit, white spirit, P1 or xylene!
1 relay (changeover contact)
for Type 701060/XX1-XX
150,000 operations at 10A 250V AC 50Hz resistive load
2 relays (make contacts)
for Type 701060/XX2-XX
100,000 operations at 5A 250V AC, 50Hz resistive load
Supply voltage 230V AC +10/-15%, 48 63Hz or 115V AC +10/-15%, 48 63Hz (isolated from measurement input)
12 24V DC +15/-15%, 24V AC +15/-15%, 48 63Hz (not isolated from measurement input)
Power consumption <3VA