6 Technical data
17
Output
Supply
Housing
Electrical data
Relais K1 (changeover contact) 150,000 operations at 10A/250V AC 50Hz resistive load
800,000 operations at 3A/250V AC 50Hz resistive load
Supply voltage 230V AC +10/-15%, 48 63Hz or 115V AC +10/-15%, 48 63Hz
(isolated from measurement input)
12 24V DC +15/-15%, 24V AC +15/-15%, 48 63Hz
(not isolated from measurement input)
Power consumption < 2VA
Material polycarbonate
Mounting DIN rail 35mm x 7.5mm to EN 50 022
Operating position unrestricted
Weight approx. 110g
Protection IP20
Flammability class UL 94 V0
Data backup EEPROM
Connection
screw terminals for wire cross-sections up to 2.5 mm
2
Electromagnetic compatibility
interference emission
immunity to interference
EN 61 326
Class B
to industrial requirements
Electrical safety EN 61 010, Part 1, overvoltage category III, pollution degree 2