User Manual
6 Technical data
15
6 Technical data
Meas. input Designation Range Meas. accuracy
1
/
ambient tempera-
ture error
Recognition of ...
Probe short-
circuit
Probe break
Resistance
thermometer
Pt100 EN 60 751 -200 to +600°C 0.1%/ ≤100ppm/°C yes yes
Pt1000 EN 60 751 -200 to +600°C 0.1%/ ≤100ppm/°C yes yes
KTY2X-6 (PTC) -50 to +150 °C 1%/ ≤100ppm/°C yes yes
Resistance 0 — 3000 Ω customer table
3
0.1%/ ≤100ppm/°C
3
= 0Ω yes
Measuring current with Pt100: 0.2 mA, with Pt1000, KTY2X-6 and resistance: 0.02 mA
Lead compensation is settable via the parameter Lead compensation resistance .
Total resistance (sensor+lead) must not exceed 320Ω with Pt100 and 3200Ω with Pt1000, KTY2X-6 and resistance.
Thermo-
couples
Fe-Con J EN 60 584 -200 to +999 °C 0.4%/ ≤100ppm/°C
2
no yes
Fe-Con L DIN 43 710 -200 to +900 °C 0.4%/ ≤100ppm/°C
2
no yes
NiCr-Ni K EN 60 584 -200 to +999 °C 0.4%/ ≤100ppm/°C
2
no yes
-10 to 60 mV customer table
3
0.1%/ ≤100ppm/°C
3
no yes
For the voltage input (-10 to 60 mV), the terminal temperature compensation for thermocouples can be used.
Internal terminal temperature compensation can be switched off through the setup program (0°C).