Electrical data
Operating data
Switching element
1, 2, 3, or 4
single-pole
snap-action switches
EM.-1...
EM.-2...
EM.-3...
EM-20
EM-30
EM.-4...
EM.-5...
EM-40
EM-50
EM.-4.../U
EM.-5.../U
EM-40/U
EM-50/U
Microswitch with
changeover contact
Microswitch with N/C contact
and restart lock
Microswitch with N/C contact,
restart lock,
and additional signal contact
Max. contact rating Switching function
Switching differential
N/C contact,
terminal 2
N/O contact,
terminal 4
TR, TW, STW (STB)
2.5%, 5%, 6%, 7%, 10%
AC 230 V +10 %
16 (3) A, cos ϕ = 1 (0.6)
DC 230 V +10 %, 0.25 A
AC 230 V +10 %
8 (1.5) A, cos ϕ = 1 (0.6)
DC 230 V +10 %, 0.25 A
TB, STB
AC 230 V +10 %
2(1)A, cos ϕ = 1 (0.6)
DC 230 V +10 %, 0.25 A
TR, TW
1%, 3%
AC 230 V +10 %, 6 (2) A, cos ϕ = 1 (0.6)
DC 230 V +10 %, 0.25A
TR, TW
2.5 %
Microswitch with gold plating, extra code "702"
AC/DC24V, 0.1A
Contact reliability To ensure the greatest possible switching reliability we recommend a minimum load of:
For silver contacts:
AC/DC = 24 V, 100 mA
For gold-plated contacts (abbreviation "702"):
AC/DC = 10 V, 5 mA
Rating surge voltage 2500 V (via the switching contacts 400 V)
Overvoltage category II
Required fuse rating See max. switching capacity
Electrical connection Standard Tab connector A 6.3 × 0.8 DIN 46 244
Extra code 699 Screw connection up to 2.5 mm
2
conductor cross section
(available at extra cost) - also suitable for retrofitting -
Switching differential
in % from the
control range/
limit value range
Switching function With liquid-filled measuring system
Rated value Possible actual value
TR, TW 2.5 approx. 2.5 - 3.5 Standard
5 approx. 5 - 6 Upon request
7 approx. 7 - 8 Upon request
1 approx. 1 - 2 Surcharge
With gas-filled measuring system
5 approx. 5 - 11 Standard
6 approx. 6 - 14 Upon request
10 approx. 10 - 16 Upon request
3 approx. 2.5 - 4 Surcharge
STW (STB) With liquid-filled measuring system
5 approx. 5 - 7 Standard
With gas-filled measuring system
6 approx. 6 - 16 Standard
Sequence contact
gap on multi-pole
version
With switching differential Sequence contact gap relative to scale range Switching point accuracy
of the sequence contact
gaps from the scale rangeMinimum Maximum
1%
2.5 %
3%, 5%
6 %, 7 %, 10 %
1%
1%
2%
3%
According to
control range table
1%
1%
<2%
<3%
The spacing of the additional contacts can be specified in °C in relation to the setpoint of contact 1.
Prefix - = switching before reaching the setpoint value
Prefix + = switching after reaching the setpoint value
For the synchronized version, specify "0" as the sequence contact gap