Datasheet
V7.00/EN/00544548
Page 2/10Data Sheet 401002
-802*PE+&R.*
'HOLYHU\DGGUHVV 0DFNHQURGWVWUDH
)XOGD*HUPDQ\
3RVWDODGGUHVV
)XOGD*HUPDQ\
3KRQH
)D[
(PDLO PDLO#MXPRQHW
,QWHUQHW ZZZMXPRQHW
-802,QVWUXPHQW&R/WG
-802+RXVH
7HPSOH%DQN5LYHUZD\
+DUORZ(VVH[&0'<8.
3KRQH
)D[
(PDLO VDOHV#MXPRFRXN
,QWHUQHW ZZZMXPRFRXN
-8023URFHVV&RQWURO,QF
0\HUV5RDG
(DVW6\UDFXVH1<86$
3KRQH
)D[
(PDLO LQIRXV#MXPRQHW
,QWHUQHW ZZZMXPRXVDFRP
40100200T10Z001K000
Technical data
General Information
Measuring range and accuracy
Reference conditions DIN 16086 and DIN EN 60770
Sensor
Measuring principle Thick film on ceramic bodies (piezo-resistive)
Admissible load changes > 10 million, 0 to 100 % measuring range
Mounting position Any
Calibration position Device upright, process connection at the bottom
Measuring range Linearity
a
Accuracy at Long-term
stability
b
Overload
capacity
c
Burst
pressure
20 °C
d
-10 to +85 °C
e
-20to+100°C
e
% MSP
f
% MSP % MSP % MSP % MSP
per year
bar bar
0 to 1.6 bar relative pressure 0.25 0.5 0.65 1 0.2 6 12
0 to 2.5 bar relative pressure 612
0 to 4 bar relative pressure 0.35 0.5 12 25
0 to 6 bar relative pressure 12 25
0 to 10 bar relative pressure 20 38
0 to 16 bar relative pressure 50 75
0 to 25 bar relative pressure 50 75
0 to 40 bar relative pressure 120 200
0 to 60 bar relative pressure 120 200
-1 to +0.6 bar relative pressure 0.5 0.65 6 12
-1 to +1.5 bar relative pressure 612
-1 to +3 bar relative pressure 0.35 0.5 12 25
-1 to +5 bar relative pressure 12 25
-1 to +9 bar relative pressure 20 38
-1 to +15 bar relative pressure 50 75
-1 to +24 bar relative pressure 50 75
a
Linearity according to limit point setting
b
Reference conditions EN 61298-1
c
All pressure transmitters are vacuum-proof.
d
Includes: linearity, hysteresis, repeatability, deviation of measuring range initial value and measuring range end value
e
Includes: linearity, hysteresis, repeatability, deviation of measuring range initial value and measuring range end value, thermal effect on mea-
suring range start and measuring span
f
MSP = Measuring span