Datasheet
JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany
Phone: +49 661 6003-0
Fax: +49 661 6003-607
Email: mail@jumo.net
Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM 20 2DY, UK
Phone: +44 1279 63 55 33
Fax: +44 1279 62 50 29
Email: sales@jumo.co.uk
Internet: www.jumo.co.uk
JUMO Process Control, Inc.
6733 Myers Road
East Syracuse, NY 13057, USA
Phone: +1 315 437 5866
Fax: +1 315 437 5860
Email: info.us@jumo.net
Internet: www.jumousa.com
V2.00/EN/00541512
Page 9/18Data Sheet 202552
20255200T10Z002K000
Outputs
Display
Electrical data
Relay (changeover) PSU board
Contact rating 5 A at AC 240 V resistive load
Contact service life 350,000 operations at nominal load/750,000 operations at 1 A
Voltage supply for
2-wire transmitter
PSU board Electrically isolated, non-controlled
DC 17 V at 20 mA, open-circuit voltage approx. DC 25 V
Voltage supply for
inductive proximity switch
Optional board DC 12 V; 10 mA
Relay (changeover) Optional board
Contact rating 8 A at AC 240 V resistive load
Contact service life 100,000 operations at nominal load/350,000 operations at 3 A
Relay SPST (normally open) Optional board
Contact rating 3 A at AC 240 V resistive load
Contact service life 350,000 operations at nominal load/900,000 operations at 1 A
Semiconductor relay Optional board
Contact rating 1 A at 240 V
Protective circuit Varistor
PhotoMOS
®
relay Optional board U ≤ DC 45 V
U ≤ AC 30 V
I ≤ 200 mA
Voltage Optional board
Output signals 0 to 10 V or 2 to 10 V
Load resistance R
load
≥ 500 Ω
Accuracy ≤ 0.5 %
Electrical current Optional board
Output signals 0 to 20 mA or 4 to 20 mA
Load resistance R
load
≤ 500 Ω
Accuracy ≤ 0.5 %
Type LC graphic display, blue with background lighting, 122 × 32 pixels
Voltage supply (switch-mode PSU) AC 110 to 240 V +10/-15 %; 48 to 63 Hz or
AC/DC 20to30 V; 48 to 63 Hz
Electrical safety To DIN EN 61010, Part 1
overvoltage category II, pollution degree 2
Power consumption Max. 14 VA (20 A fuse max.)
Data backup EEPROM
Electrical connection On the back via screw terminals,
conductor cross-section up to max. 2.5 mm
2
Electromagnetic Compatibility (EMC) DIN EN 61326-1
Interference emission Class A
Interference immunity To industrial requirements