7 Configuration level
2014-06-12
26
7.6 C116 Display after switch-on
7.7 C117 Binary input function
k Factory setting
Normal display Comment
0 Limit value Chapter “Overview of operation”
1 Measured value
2 Warning alarm
3 Limit for the differential Can only be set when C111 = 24
(differential measurement) is set.
4 Differential
5 Measured value 2
Binary input function Comment
0 inactive
1 Unlocking The binary input has the same function as the "Reset" key
2 Keyboard inhibit To prevent unauthorized device operation
3 Level inhibit Configuration and parameter levels are inhibited.