Operating Manual Owner manual
7 Configuration level
2014-06-12
22
kFactory setting
037
W3Re-W25Re D Thermocouple -1999 to +9999°C -5 to +2500°C
039
Cu-CuNi T Thermocouple EN 60584 -1999 to +9999°C -205 to +405°C
040
Fe-CuNi J Thermocouple EN 60584 -1999 to +9999°C -205 to +1205°C
041
Cu-CuNi U Thermocouple DIN 43710 -1999 to +9999°C -205 to +605°C
042
Fe-CuNi L Thermocouple DIN 43710 -1999 to +9999°C -205 to +905°C
043
NiCr-Ni K Thermocouple EN 60584 -1999 to +9999°C -205 to +1377°C
044
Pt10Rh-Pt S Thermocouple EN 60584 -1999 to +9999°C -5 to +1773°C
045
Pt13Rh-Pt R Thermocouple EN 60584 -1999 to +9999°C -5 to +1773°C
046
Pt30Rh-Pt6Rh B Thermocouple EN 60584 -1999 to +9999°C 295 to 1825°C
048
NiCrSi-NiSi N Thermocouple EN 60584 -1999 to +9999°C -105 to +1305°C
052
0 to 20 mA -1999 to +9999°C 0 to 21mA
053 4 to 20 mA -1999 to +9999°C 3.6 to 21mA
063 0 to 10 V -1999 to +9999°C 0 to 10.5 V
071 2 to 10 V -1999 to +9999°C 1.8 to 10.5V
v Chapter 10.4 “Restricting the setting
range for the AL limit (minimum/maximum
value master)”
Analog input Comment
Setting range for AL:
(can be restricted via
setup)
Limits for
overrange/
underrange