Operating Manual Owner manual

7 Configuration level
2014-06-12
20
7.1 C111 Analog inputs
Analog input Comment
Setting range for AL:
(can be restricted via
setup)
Limits for
overrange/
underrange
001 Pt 100
EN 60751
in 3-wire circuit -1999 to +9999°C -205°C/ +855°C
006 Pt 1000
EN 60751
in 3-wire circuit -1999 to +9999°C
-205°C/ +855°C
601 KTY11-6 PTC sensor in 2-wire circuit -1999 to +9999°C -55°C/ +155°C
003 Pt 100
EN 60751
in 2-wire circuit -1999 to +9999°C
-205°C/ +855°C
005 Pt 1000
EN 60751
in 2-wire circuit -1999 to +9999°C
-205°C/ +855°C
024 2x Pt 100 DIN for differential measurement -1999 to +9999°C -205°C/ +855°C
The TB/TW can measure the differential of two Pt 100 resistance thermometers in a 2-wire
circuit.
Measurement input INP (terminal 1 and 2) acquires the first temperature.
The second measurement input IN2 (terminal 2 and 3) acquires the second temperature.
The differential DIF = INP - IN2 is displayed and evaluated.
Setting range for ALD: -1999 to 9999
k Factory setting