the transmitter. The requirements from Table 1 of EN 13463-6 apply. The signal is fed in via the 4 to 20 mA input.
v Setting is according to Chapter 8.2.2 onwards
The limit value must be determined according to the relevant use and/or application. The value must be set so that no danger-
ous state can occur when all relevant factors such as response time and, if applicable, measurand overshoot of the monitored
apparatus including the JUMO safetyM STB/STW Ex and transmitter are taken into account.
To prevent unintended changes to the set parameters, there is an option to seal the JUMO safetyM STB/STW Ex according to
Chapter 5.8 of this Operating Manual or to use a keypad lock or level inhibit according to Chapter 8.4.