Operating Manual Owner manual

Table Of Contents
8 Configuration level
99
2013-04-01
8.5.5 Error signal
If, for the measured value 1 or 2, the value is exceeded,
not reached, or a diagnostic error occurs, the current or
voltage value set on the analog output is output as a
so-called error signal.
For signal type 4 to 20 mA 3.4 or 21.2 mA
For signal type 0 to 20 mA 0 or 21.2 mA
For signal type 2 to 10 V 1.7 or 10.4 V
For signal type 0 to 10 V 0 or 10.4 V
Parameter Comment
Value range
(factory setting in bold)