Connection diagram
The connection diagram contained in the data sheet provides preliminary information about the connection possibilities. For electrical
connection, only use the installation instructions or the operating manual. The knowledge and the correct technical execution of the
safety information/instructions contained in these documents are a prerequisite for installation, electrical connection and commission-
ing/start-up as well as for safety during operation.
Connection is carried out via screw terminals. Lead Admissible cross
section
1 wire 2.5 mm
2
fine-strand,
with core-end ferrule
1.5 mm
2
Legend Remark Screw terminals Screw terminals
1, 2
Analog input 1 Analog input 2
Thermocouple/
Double thermocouple
RTD temperature probe in 2-wire circuit
RTD temperature probe Pt100/Pt1000 in 3-wire cir-
cuit
RTD temperature probe Pt100 in
2-wire circuit, individual sensor for both analog inputs
Caution:
When only one probe (SIL2) is connected, the temperature limitation device is reduced from SIL3 to SIL2! However, the internal 2-channel structure
(1oo2D) in the device is still retained. Both channels measure the same sensor due to the simplified external circuit.
(4) ... 20 mA
(4) ... 20 mA for both analog inputs
Caution:
When only one probe (SIL2) is connected, the temperature limitation device is reduced from SIL3 to SIL2! However, the internal 2-channel structure
(1oo2D) in the device is still retained. Both channels measure the same current signal due to the simplified external circuit.
+
–
2
3
+
–
7
8
J
13
J
68
A
Enter the lead resistance for RTD temperature probes in 2-wire circuit when using
greater line lengths.
Setup program: edit => analog inputs
123
J
678
J
J
13 68
2
3
+
–
I
x
7
8
+
–
I
x
2
+
–
I
x
7