Datasheet
Page 11/13
Data Sheet 701150
2011-04-21/00540116
JUMO GmbH & Co. KG
Delivery address:Mackenrodtstraße 14,
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany
Phone: +49 661 6003-0
Fax: +49 661 6003-607
e-mail: mail@jumo.net
Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax: +44 1279 635262
e-mail: sales@jumo.co.uk
Internet: www.jumo.co.uk
JUMO Process Control, Inc.
8 Technology Boulevard
Canastota, NY 13031, USA
Phone: 315-697-JUMO
1-800-554-JUMO
Fax: 315-697-5867
e-mail: info@jumo.us
Internet: www.jumo.us
Failure rates and SSF for 70.1150...23 (AC240V)
Failure rates and SSF for 70.1150...25 (AC/DC24V)
The PFH and PFD
avg
values were calculated assuming that the time to restore the system is 8h (MTTR = 72h). Furthermore, the calculation was
based on a lifetime of 10 years (T
1
= 10y). The common cause factor was determined as per the tables of the DIN EN 61508 for sensor systems
and logics.
Calculations DIN EN ISO 13849-1 Performance Level PL d - Low voltage 230V
Calculations DIN EN ISO 13849-1 Performance Level PL d - Safety extra low voltage 24V
3. The MTTF
d
value of a partial system must be limited to 100 years as per the DIN EN ISO 13849-1 requirements.
Vari--
ant
s
[Fit]
dd
[Fit]
dd
[Fit]
SSF PFH (1/
h)
PFD
avg
1 917.24 278.5 89.80 93.01% 1.04 e
-8
2.59 e
-4
2 917.24 278.5 89.80 93.01% 7.47 e
-9
1.03 e
-4
3 930.69 301.37 91.74 93.07% 7.95 e
-9
1.04 e
-4
4 936.75 318.41 93.64 93.06% 8.40 e
-9
1.08 e
-4
5 930.09 291.77 89.94 93.14% 7.67 e
-9
9.97 e
-5
Vari--
ant
s
[Fit]
dd
[Fit]
dd
[Fit]
SSF PFH (1/
h)
PFD
avg
1 851.33 278.98 90.7 92.57% 1.05 e
-8
2.60 e
-4
2 851.33 278.98 90.7 92.57% 7.53 e
-9
1.04 e
-4
3 876.32 301.85 93.48 92.65% 8.07 e
-9
1.06 e
-4
4 882.38 318.89 95.38 92.65% 8.51 e
-9
1.10 e
-4
5 868.03 300.5 91.54 92.74% 7.78 e
-9
1.02 e
-4
Variant MTTF
d
DC
avg
CCF
1 100 years
3
(310 years) 76% 80
2 100 years
3
(310 years) 76% 80
3 100 years
3
(290 years) 77% 80
4 100 years
3
(300 years) 76% 80
5 100 years
3
(299 years) 76% 80
Variant MTTF
d
DC
avg
CCF
1 100 years
3
(309 years) 75% 80
2 100 years
3
(309 years) 75% 80
3 100 years
3
(289 years) 76% 80
4 100 years
3
(299 years) 76% 80
5 100 years
3
(291 years) 77% 80