Data Sheet 703041JUMO GmbH & Co. KG ˘ 36035 Fulda, Germany Page 4/10
Technical data
Thermocouple input
Input for resistance thermometer
Input for standard signals
Logic inputs
Measuring circuit monitoring
In the event of a fault, the outputs move to a defined (configurable) status.
Designation Measuring range Measuring accuracy Ambient
temperature error
Fe-Con L
Fe-Con J
Fe-Con U
Cu-Con T
NiCr-Ni K
NiCr-Con E
NiCrSi-NiSi N
Pt10Rh-Pt S
Pt13Rh-Pt R
Pt30Rh-Pt6Rh B
W5Re-W26Re C
W3Re-W25Re D
W3Re-W26Re
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
-200 to + 900°C
-200 to +1200°C
-200 to + 600°C
-200 to + 400°C
-200 to +1372°C
-200 to +1000°C
-100 to +1300°C
0 to 1768°C
0 to 1768°C
0 to 1820°C
0 to 2320 °C
0 to 2495 °C
0 to 2400 °C
≤0.25%
≤0.25%
≤0.25%
≤0.25%
≤0.25%
≤0.25%
≤0.25%
≤0.25%
≤0.25%
≤0.25% in the range 300 to 1820°C
≤0.25%
≤0.25%
≤0.25%
100 ppm /°C
100 ppm /°C
100 ppm /°C
100 ppm /°C
100 ppm /°C
100 ppm /°C
100 ppm /°C
100 ppm /°C
100 ppm /°C
100 ppm /°C
100 ppm /°C
100 ppm /°C
100 ppm /°C
Cold junction Pt100, internal
Designation Connection Measuring range Measuring accuracy Ambient
temperature error
3-/4-wire 2-wire
Pt100 EN 60751 (factory setting) 2-wire / 3-wire / 4-wire -200 to +850°C ≤0.05% ≤0.4% 50 ppm / °C
Pt500 EN 60751 2-wire / 3-wire / 4-wire -200 to +850°C ≤0.2% ≤0.4% 100 ppm /°C
Pt1000 EN 60751 2-wire / 3-wire / 4-wire -200 to +850°C ≤0.1% ≤0.2% 50 ppm /°C
KTY11-6 2-wire -50 to +150°C ≤2.0% 50 ppm /°C
Sensor lead resistance max. 30Ω per lead for 3-wire or 4-wire circuit
Measuring current approx. 250µA
Lead compensation Not required for 3-wire or 4-wire circuit. With a 2-wire circuit, the lead resistance can be
compensated in software by a correction of the process value.
Designation Measuring range Measuring
accuracy
Ambient
temperature error
Voltage 0(2) — 10 V
0—1V
Input resistance R
IN
> 100kΩ
≤0.05%
≤0.05%
100 ppm / °C
100 ppm / °C
Current 0(4) — 20mA, voltage drop 2.0 — 2.5V ≤0.05% 100 ppm / °C
Heating current 0 — 50mA AC ≤1% 100 ppm / °C
Resistance transmitter min. 100Ω, max. 4kΩ ±4Ω 100 ppm / °C
Floating contacts
Sensor Overrange /
underrange
Probe or lead short-circuit Probe or lead break
Thermocouple • - •
Resistance thermometer • • •
Voltage 2 — 10V
0 — 10V
0 — 1V
•
•
•
•
-
-
•
-
-
Current 4 — 20mA
0 — 20mA
•
•
•
-
•
-
Resistance transmitter - - •
• = recognized - = not recognized