Block structure
Analog input
Option 1
Option 2
2 logic inputs
2 relays (changeover)
2 logic outputs
Supply voltage
17V / 20mA
for 2-wire transmitter
Option 3
only for type 703042/43/44
only at type 703042/43/44
(make contact at type 703041)
Option boards:
Analog input
–2 logic inputs
1 relay 230V/8A (changeover)
2 relays 230V/3A (make contact)
with common pole
1 solid-state relay
Analog output (voltage/current)
RS422/485 interface
–PROFIBUS-DP interface
JUMO dTRON 304/308/316
Compact Controller
with program function
Brief description
The JUMO dTRON 300 series of controllers includes four freely programmable devices in
different DIN formats for controlling temperature, pressure and other process variables. As a
temperature controller (TR) according to EN 14597 the devices are used in heat-generating
plants to control the temperature of liquids or gases (mode of action: 1B).
The high-contrast, multicolor LC display for process value, setpoint and operator prompting
contains two four-digit 7-segment displays, two single-character 16-segment displays, display
of the active setpoints, six switch position indicators, and displays for the dimensional unit,
ramp function and manual operation.
Simple operation through 4 keys. The instruments can be used as 2-state, 3-state, modulating
or continuous controllers. The controller software includes a program or ramp function,
parameter set changeover, two autotuning (self-optimization) procedures, a math and logic
module, as well as 4 limit comparators.
Linearizations for the usual transducers are stored, and a customer-specific linearization table
can be programmed.
A setup program is available for user-friendly configuration from a PC.
A serial interface for RS422/485 or Profibus-DP can be used to integrate the instruments into a
data network.
The electrical connection is made at the back, via screw terminals.
The possible input and output configurations are shown in the following block diagram. The
option boards are universally applicable for all instruments in the series.
JUMO dTRON 304
Type 703044/ ...
JUMO dTRON 308Q
Type 703043/ ...
JUMO dTRON 308H
Type 703042/ ...
JUMO dTRON 316
Type 703041/ ...
Key features
+
Up to two programmable analog inputs
+ Four programmable setpoints,
two parameter sets
+ Program function with 8 segments,
or ramp function
+ Math and logic module
+ 4 limit comparators
+ Two tim ers
+ Two self-optimization procedures
+ Fast, user-friendly configuration through
the setup program with program editor
+ RS422/485 interface or
PROFIBUS-DP interface
Approvals/marks of conformity (see technical data)