Manual
Operator responsibility – Safety instructions
8
2.4. Technical specifications
(with T-pump) FC1200T FCW1200T
Working temperature range °C -10 ... 80 -10 ... 80
Cooling capacity °C 20 10 -10
(water-glycol) kW 0.11 0.75 0.15
Refrigerant R134a
Heater capacity kW 1.2
Pump capacity:
Pressure max. bar 3.5
Flow rate max. Lpm 28
Pump connections M16x1
Noise level, 1 m distance dBA 58 53
Filling volume l 8 ... 11
Dimensions (WxLxH) cm 46 x 61 x 49
Ambient temperature °C 5 ... 40
Shipping weight kg 67 69
Mains power connection V/Hz 208-230/60 or 230/50
Total power consumption W 2600
(with T-pump) FC1600T FCW1600T
Working temperature range °C -15 ... 80 -15 ... 80
Cooling capacity °C 20 10 -10
(water-glycol) kW 1.45 1.05 0.25
Refrigerant R134a
Heater capacity kW 1.2
Pump capacity:
Pressure max. bar 3.5
Flow rate max. Lpm 28
with tubing connections mm dia. 13.5 / 9.5
Pump connections M16x1
Noise level, 1 m distance dBA 58 53
Filling volume l 8 ... 11
Dimensions (WxLxH) cm 46 x 61 x 49
Ambient temperature °C 5 ... 40
Shipping weight kg 67 69
Mains power connection V/Hz 208-230/60 or 230/50
Total power consumption W 2700
All data have been determined at rated voltage and frequency
ambient temperature: 20 °C bath liquid: water-glycol