Owner manual

8
GF 100 DV II Nordic QT
GF 200 DV II Lillehammer
Stove and Vent Clearance
Requirements
Minimum Clearances from the Stove to Combustibles:
Measured from the stove top plate. See figs. 2-4.
For Both Stoves
Rear: 0” (0 mm)
Ceiling: 42” (1066 mm)
Corner: 2” (50 mm)
Sides: 3” (76 mm)
Minimum Clearances between Vent Pipe and
Combustible Materials:
Horizontal Run:
Off the top of the pipe 2” (50 mm)
Off the sides and bottom 1” (25 mm)
Vertical Run:
All sides 1” (25 mm)
Figure 3. Mantel Clearances - stove flush with fireplace face.
Figure 4. Mantel Clearances - stove set back into fireplace,
6 1/2” maximum.
Figure 2. Alcove Installation Clearances.
CLEARANCE TO REAR WALL = ZERO (0”)
GF 100 DV
or
GF 200 DV
Max. Depth
24”
(610mm)
Alcove Installation
Maximum Alcove Depth: 24” (610 mm)
Minimum Alcove Width: 34” (864 mm)
Minimum Ceiling Height
from stove top: 42” (1066 mm)
Min. 34”
(864 mm)
Plinth Kit: 23 3/4 in. (603 mm)
Long Legs: 27 in. (686 mm)
GF 100 DV II GF 200 DV II
Nordic QT Lillehammer
A 49 in. (1245 mm) 51 1/2 in. (1308 mm)
B 47 1/2 in. (1206 mm) 50 in. (1270 mm)
C 46 in. (1168 mm) 48 1/2 in. (1232 mm)
D 44 1/2 in. (1130 mm) 47 in. (1194 mm)
E 43 in. (1092 mm) 45 1/2 in. (1156 mm)
F 17 3/4 in. (451 mm) 17 3/4 in. (451 mm)
G 22 1/4 in. (565 mm) 24 3/4 in. (629 mm)
Plinth Kit: 23 3/4 in. (603 mm)
Long Legs: 27 in. (686 mm)
GF 100 DV II GF 200 DV II
Nordic QT Lillehammer
A 50 in. (1270 mm) 52 1/2 in. (1333 mm)
B 48 1/2 in. (1232 mm) 51 in. (1295 mm)
C 47 in. (1194 mm) 49 1/2 in. (1257 mm)
D 45 1/2 in. (1156 mm) 48 in. (1219 mm)
E 44 in. (1118 mm) 46 1/2 in. (1181 mm)
F 4 1/4 in. (108 mm) 4 1/4 in. (108 mm)
G 22 1/4 in. (565 mm) 24 3/4 in. (629 mm)
11.5
9.5
7.5
5.5
Max. Mantel
Depth
Min. Mantel
Depth
Max. Top Trim
Depth = 1
3.5
A
C
E
BD
F
G
11.5
9.5
7.5
5.5
Max. Mantel
Depth
Min. Mantel
Depth
Max. Top Trim
Depth = 1
3.5
A
C
E
BD
F
G
Max.
6 1/2