Installation and Operation Instructions gas heater GF 100 DV II Nordic QT, GF 200 DV II Lillehammer
14
GF 100 DV II Nordic QT
GF 200 DV II Lillehammer
Figure 17. Vent Terminal Clearances - National Fuel Gas Code.
Horizontal Termination Clearance
A = Clearance above grade, veranda, porch , deck, or
balcony : 12 inches (30 cm) minimum.
B = Clearance to window or door that may be opened:
**Min. 9 inches, U.S. / *12 inches (30 cm) CAN.
We recommend 12in. minimum to prevent condensa-
tion on the window.
C = Clearance to permanently closed window:
**Min. 9 inches, U.S. / *12 inches (30 cm) CAN
We recommend 12 in. minimum to prevent condensa-
tion on the window.
D = Vertical clearance to ventilated soffit located above
the terminal within a horizontal distance of 2 feet (60 cm)
from the centerline of the terminal: 18 inches
(46 cm) minimum.
E = Clearance to unventilated soffit: 12 inches (46 cm)
minimum.
F = Clearance to outside corner: **Min. 9 inches, U.S. / *12
inches (30 cm) CAN. We strongly recommend 12 inches,
particularly where windy conditions pevail.
G = Clearance to inside corner: ** Min. 6 inches, U.S. / *12
inches (30 cm) CAN. We strongly recommend 12 inches,
particularly where windy conditions pevail.
H = *Not to be installed within 15 feet (4.5 m) above a
meter/regulator assembly within 3 feet (90 cm)
horizontally from the center-line of the regulator.
* In accordance with CSA B149.1 Installation Codes.
** In accordance with the current ANSI Z223.1/NFFPA 54,
National Fuel Gas Code. Note: Local Codes and Regulations may
require different clearances.
1
A vent shall not terminate directly above a sidewalk or driveway
which is located between two single family dwellings and serves
both dwellings.
2
Only permitted if veranda, porch, deck, or balcony, is fully open
on a minimum of two sides beneath the floor.*
I = Clearance to service regulator vent outlet:
3 feet (91 cm) minimum.
J = Clearance to nonmechanical air supply inlet to building or
the combustion air inlet to any other appliance:
12 inches (30 cm) minimum.
K = Clearance to a mechanical air supply inlet:
**Min. 3 feet (91 cm) above if within 10 feet horizontally,
U.S. / *6 feet (1.83 m) minimum / CAN
L =
1
Clearance above paved sidewalk or a paved driveway
located on public property: 7 feet (2.1 m) min.
M = Clearance under veranda, porch, deck, or balcony:
12 inches (30 cm) minimum.
2