Instruction Manual

WWW.JOHNSONSYSTEMS.COM 9
120 = 120VAC 1Ø 3-Wire via a Single 5' Edison Power Cord
Includes a single factory installed 5' (1.5m) Edison power cord. Connect the
cables to a standard Edison (NEMA 5-15) receptacle, protected with a circuit
breaker rated at a maximum of 15 Amps.
Up to 15 Amps – maximum 1,800W total.
Internal electrical wiring termination is not required.
Available only with Duplex Edison output connectors/receptacles.
120 = 120VAC 1Ø 3-Wire via Dual 5' Edison Power Cord
Includes two (2) factory installed 5' (1.5m) Edison power cords. Connect the
cables to standard Edison (NEMA 5-15) receptacles, each protected with a
circuit breaker rated at a maximum of 15 Amps.
2 circuits of up to 15 Amps – maximum 3,600W total.
Internal electrical wiring termination is not required.
Dimmers 1, 3 and 5 are powered from a single power cord.
Dimmers 2, 4 and 6 are powered from a single power cord.
Available only with Duplex Edison (NEMA 5-15) output connectors/
receptacles.
120/240 = 120/240VAC 1Ø 4-Wire Terminal Block
Up to 40 Amps per phase – maximum 9,000W total.
Use wire size #12 to #4 AWG copper wire only, rated for 167°F (75°C)
minimum.
Strip insulation length to 0.44" (11mm).
Torque power terminals (A, B, N, ) to 10.5 IN-LBS (1.2 NM).
Dimmers 1, 3 and 5 are powered from Phase A.
Dimmers 2, 4 and 6 are powered from Phase B.
120/208 = 120/208VAC 3Ø 5-Wire Terminal Block
Up to 30 Amps per phase – maximum 9,000W total.
Use wire size #12 to #4 AWG copper wire only, rated for 167°F (75°C)
minimum.
Strip insulation length to 0.44" (11mm).
Torque power terminals (A, B, C, N, ) to 10.5 IN-LBS (1.2 NM).
Dimmers 1 and 4 are powered from Phase A.
Dimmers 2 and 5 are powered from Phase B.
Dimmers 3 and 6 are powered from Phase C.
WARNING: Ensure all AC power supply connections are tightened to the
torque specication provided, before turning on the AC power
supply!
Ensure all chassis panels are secure before turning on the AC
power supply!