Instruction Manual

www.johnsonsystems.com 35
44. RESTORE Restore parameters saved in the EEPROM memory module.
All of the conguration setting parameters can be restored from the EEPROM
memory module if they have been inadvertently changed or corrupted. This feature
can also be used to load conguration setting parameters into a different or new
control module. This reduces the conguration time for multi-system applications that
require similar settings or when a replacement control module is required.
Press EXECUTE to enter the menu.
DISABLED This menu is disabled for inadvertent use. Proceed to enable.
ENABLED Press and hold MENU ( ) and MENU ( ) at the same time for 4-5 seconds.
MEMCHECK Automatically checks the EEPROM memory module for parameter type.
OKAY.... The EEPROM memory module has been veried for parameter type.
PROCEED? Press EXECUTE to proceed.
SURE ??? Press EXECUTE to proceed.
CRC-TEST Automatically does a CRC test on the parameter code in the EEPROM.
WAIT CRC test in progress.
VERIFY CRC test in progress.
DONE!! CRC test is done and the parameter restore automatically begins.
WILL Parameter restore in progress.
AUTO Parameter restore in progress.
RESTART When parameter restore is complete, the system restarts.
SERIAL # Displayed when the silicone serial number on the EEPROM memory module is a
mismatch with the silicone serial number on the MADD-96 microcontroller.
PROCEED? Press EXECUTE to proceed.
NO MEM! Displayed if an EEPROM memory module is not detected.
WRONG Displayed if the wrong type (parameter) of EEPROM memory module detected.
MEM TYPE Displayed if the wrong type (parameter) of EEPROM memory module detected.
WRONG Displayed if the wrong product type of EEPROM memory module detected.
PRODUCT Displayed if the wrong product type of EEPROM memory module detected.
ERROR Displayed when an error occurs. Waits for key press to restart RESTORE.
45. BACKUP Backup parameters and save them in the EEPROM memory module.
All of the conguration setting parameters can be saved in the EEPROM memory
module for backup. The backup parameters can then be restored if they have been
inadvertently changed or corrupted. Once backup is complete the EEPROM memory
module may be removed for safe storage. All DE90-3000 Series retrot control
systems are shipped with the factory default settings saved in the EEPROM memory
module.
Press EXECUTE to enter the menu.
DISABLED This menu is disabled for inadvertent use. Proceed to enable.
ENABLED Press and hold MENU ( ) and MENU ( ) at the same time for 4-5 seconds.
MEMCHECK Automatically checks the EEPROM memory module for parameter type.
SURE ??? Press EXECUTE to proceed.
WAIT Automatically begins parameter backup and generates CRC value.
VERIFY Automatically veries parameter backup data and CRC value.
DONE!! Parameter backup is done and saved in the EEPROM memory module.
NO MEM! Displayed if an EEPROM memory module is not detected.
WRONG Displayed if the wrong type (parameter) of EEPROM memory module detected.
MEM TYPE Displayed if the wrong type (parameter) of EEPROM memory module detected.
WRONG Displayed if the wrong product type of EEPROM memory module detected.
PRODUCT Displayed if the wrong product type of EEPROM memory module detected.
DATA ERR Displayed when a data error occurs. Waits for key press to restart BACKUP.
NOTE: Backup all DE90-3000 Series retrot control systems when conguration is
complete.