29. S-ALARM Select the level and control channels triggered by the security alarm input.
When a contact is sensed on the security alarm input, selected control channels will
cycle on and off at a 1 hertz rate. The level of the on cycle can be set from 0% to
100%. The security alarm input takes precedence over the DMX and analog inputs.
The system will stay in security alarm mode until the contact is removed.
Press EXECUTE to enter the menu and congure the security alarm input.
L>FL:01* Displays the output level (L>FL) of 100% and control channel (01*).
L>00:01* Press MENU ( ) to change the output level from 00% to 100% (FL).
L>FL:01* Press MENU ( ) at the same time to toggle the level back to 100% (FL).
L:FL>01* Press EXECUTE to toggle the pointer (>) and select the control channel(s).
L:FL>24* Press MENU ( ) to select the desired control channel from 01 to 24.
L:FL>24 Press EXECUTE to toggle the ag (*) for each desired control channel.
Press ESCAPE to exit the menu and save the desired settings.
Press RESET to exit the menu without saving.
The menu will automatically timeout after 2 minutes of inactivity and save.
30. F-ALARM Select the level and control channels triggered by the re alarm input.
When a contact is sensed on the re alarm input, the selected control channels are
triggered on to the selected output level from 0% to 100%. The re alarm input is
merged with the DMX and analog inputs with highest takes precedence (HTP). The
system will stay in re alarm mode until the contact is removed.
Press EXECUTE to enter the menu and congure the re alarm input.
L>FL:01* Displays the output level (L>FL) of 100% and control channel (01*).
L>00:01* Press MENU ( ) to change the output level from 00% to 100% (FL).
L>FL:01* Press MENU ( ) at the same time to toggle the level back to 100% (FL).
L:FL>01* Press EXECUTE to toggle the pointer (>) and select the control channel(s).
L:FL>24* Press MENU ( ) to select the desired control channel from 01 to 24.
L:FL>24 Press EXECUTE to toggle the ag (*) for each desired control channel.
Press ESCAPE to exit the menu and save the desired settings.
Press RESET to exit the menu without saving.
The menu will automatically timeout after 2 minutes of inactivity and save.
31. Ø-PATCH Set the zero-cross phase reference for each dimmer output circuit.
Each of the 24 dimmer control outputs can be patched to any of the incoming phase
references. The phase reference for each dimmer control output must be the same
as the incoming phase for the dimmer. If a dimmer control output is patched to the
incorrect phase reference the dimmer will not dim correctly and will go to full output at
around 1% DMX input.
The factory conguration for DE90-3000 Series retrot control systems is for three-
phase applications. The defaults (DEFAULTS) menu is used to recongure the phase
patch for standard single-phase applications.
Refer to the charts on page 8 for the standard Ø-PATCH conguration for DE90
dimmer racks.
This menu provides the ability to congure a custom Ø-PATCH for non-standard
applications.
Press EXECUTE to enter the menu and congure the dimmer phase patch.
CH 01 ØA Displays the dimmer output channel (CH 01) and patched phase (ØA).
CH 24 ØA Press MENU ( ) to change the dimmer output channel to patch from 01 to 24.
CH 24 ØB Press EXECUTE to toggle the patch to phase-B (ØB).
CH 24 ØC Press EXECUTE to toggle the patch to phase-C (ØC).
Press ESCAPE to exit the menu and save the desired settings.
Press RESET to exit the menu without saving.
The menu will automatically timeout after 2 minutes of inactivity and save.