Instruction Manual

www.johnsonsystems.com 15
+12V
+12V
Common
Analog
Input
1 Thru 4
Common
+12V
Analog
Input
1 Thru 4
Maintained
Normally
Open
Switch
Contact
Control Input/Output Connections
All DE90-3000 Series retrot control systems come with a variety of control
input and output (I/O) capabilities. All I/O connections are terminated on the
Backplane.
Breakaway type connectors are supplied for all I/O connections.
Use wire size #28 to #12 AWG. Strip insulation length to 0.3" (7.5mm).
Torque terminations to 3.6 IN-LBS (0.4 NM).
NOTE:
For connection use copper wire only, rated for 167°F (75°C) minimum.
Dual DMX Input and Thru
DMX A terminates to J1 and J2 connectors.
DMX B terminates to J3 and J4 connectors.
Complies with USITT DMX512-A (ANSI E1.11 - 2008), standard protocol
for digital data control.
Recommended cable is Belden 9829, 9842, Cat 5 or equivalent
(low-capacitance, twisted pair).
Wiring must follow a daisy-chain topology.
Maximum of 32 receiving dev-ices on a single DMX line.
Maximum cable length is 1,500 feet (455 meters).
For more information, Google DMX, or visit:
http://old.usitt.org/DMX512FAQ.aspx
NOTE: Ensure only the last (end-of-line) DMX receiving device is terminated!
+12VDC Power Supply Output
A regulated +12VDC power supply is available for powering
external devices.
Terminate on +12V and COMMON of T6 connector.
External devices should not exceed the maximum combined
current draw of 200 mA.
0-10VDC Analog Inputs or Load Shed Contact Inputs
Four (4) analog inputs terminate on J6 connector.
Inputs can be congured for normal or load shed mode of operation.
Inputs can be patched to any combination of dimmer output circuits.
Programmed in the “ANA MODE” and “ANA PTCH” menus.
See page 28 and 29 for details.