Contents Warranty...........................................................................................................2 User Manual Copies.........................................................................................2 Introduction.......................................................................................................3 Features...........................................................................................................3 CS-SA Series Control Station Diagrams......
Introduction Low voltage manual lighting controls for virtually any application! CS-SA Series 'SUPER ANALOG' Time Fade Stations The ‘Super Analog’ series of controls have been developed specifically for control of LED fixtures and next generation fluorescent ballasts requiring 0-10VDC analog control for dimming. Universal in design this series of analog controls is designed to deliver unmatched value in new or retrofit applications.
CS-SA Series Control Station Diagrams "ON", "DIM", and "OFF" Buttons With Integral LED's Master (M) Slider Secondary (3, 6, 9, or 12) Sliders 6-Position Connector (J1) For: • Power Supply Input (COM, V+) • Button Contacts (ON, DIM, RST) • Master Pot (MP) Analog Output Analog Output Voltage Level Calibration Jumper (JP1) Analog Output Connector(s) OUTPUT P1 P1 P1 P1 P2 P2 P2 P2 P3 P3 P3 P3 J1 Analog Outputs 10, 11, 12 4 Analog Outputs 7, 8, 9 Analog Outputs 4, 5, 6 Analog Outputs 1, 2, 3
“ON”, “DIM” and “OFF” Buttons with Integral LED’s All CS-SA Series control stations contain 3 buttons with integral blue LED’s. When a button is pressed, the control station is triggered into the corresponding state. The button LED’s indicate the state of the control station. Under normal operation, when a button is pressed, the corresponding LED will illuminate. If the control station is fading, the LED will flash once per second until the fade is complete.
Wiring an Independent Control Station An independent control station requires 2 conductors for V+ and common, and 1, 3, 6, 9 or 12 conductors for the analog outputs.
Wiring Two or More Master Control Stations Together with “Take Control” When two or more master control stations are controlling the same device, “take control” is typically required. When a button is pressed on one of the master control stations, it will automatically “take control” from the other master control stations and put them in the “OFF” state. Wiring between the master control stations requires 2 conductors for V+ and common, and 1 conductor for reset (RST) “take control”.
Mounting the Control Station The control station can be mounted on/in a gangable (usually masonry) type of back box with a minimum depth of 2" (50.8mm) and a preferred depth of 3.5” (88.9mm). A #2 Phillips head screwdriver is required to secure the control station, using the provided black #6-32 x 1" (25.4mm) mounting screws. NOTE: Ensure the back box is earth grounded to protect the control station from electrostatic discharge. NOTE: Ensure the back box mounting-hole threads are not damaged.
Time Fade The control station is capable of fading from: “OFF” “ON” “ON” “OFF” “OFF” “DIM” “DIM” “OFF” The control station is capable of pseudo fading from: “DIM” “ON” “ON” “DIM” The control station automatically begins fading when a button is pressed. The button LED flashes on and off once per second to indicate fading. NOTE: Pressing a button or adjusting the master slider level while the control station is fading, cancels the fade and immediately activates the button pressed.
Local Lockout Mode Activation When the local lockout mode is activated, the control station is locked in the “OFF” state. Any button press is ignored and the “OFF” LED flashes once to indicate local lockout mode is activated. Procedure: • • To activate the local lockout mode, press and hold the “OFF” button for approximately 10 seconds, until the “OFF” LED extinguishes. To deactivate the local lockout mode, press and hold the “OFF” button for approximately 10 seconds, until the “OFF” LED illuminates.
Notes www.johnsonsystems.
CS-SA 'SUPER ANALOG' Time Fade Stations Model Description # Wires Back Box Minimum PCB Clearance CS-SA-1-? 1 gang, single channel manual control w/on, present, and off 4 1 gang 1.80" W x 2.75" H x 2.00" D 4.6 cm x 7.0 cm x 5.1 cm CS-SA-3-? 2 gang, 3 channel manual control w/master slider, on, preset, and off 6 2 gang 3.60" W x 2.75" H x 2.00" D 9.1 cm x 7.0 cm x 5.1 cm CS-SA-6-? 3 gang, 6 channel manual control w/master slider, on, preset, and off 9 3 gang 5.50" W x 2.75" H x 2.00" D 14.