User Guide

VSD Series II Variable Speed Open Drives Product Bulletin
22
Auxiliary Voltage 24 V ±10%, Maximum 250 mA
Output Reference Voltage 10 V +3%, Maximum Load 10 mA
Analog Output 0 to 10 V, 0 (4) to 20 mA; R
L
max. 500 Ohms; Resolution 10 bit; Accuracy
± 2%, Dip Switch Selection (Voltage/Current)
Relay Outputs 3 Programmable, 2 Form C, 1 Form A Relay Outputs Switching Capacity: 24
VDC/8 A, 250 VAC/8 A, 125 VDC/0.4 A
Hard Wire Jumper Between Terminal 6 and 10 (Factory Default)
Dip Switch Setting Default RS485 = Off
A01 = Current
A12 = Current
A11 = Voltage
Overcurrent Protection Yes
Overvoltage Protection Yes
DC Bus Regulation Anti-trip Yes (Accelerates or Decelerates the Load)
Undervoltage Protection Yes
Earth Fault Protection Yes, in case of earth fault in motor or motor cable, only the frequency
converter is protected.
Input Phase Supervision Yes, trips if any of the input phases are missing
Motor Phase Supervision Yes, trips if any of the output phases are missing
Overtemperature Protection Yes
Motor Overload Protection Yes
Motor Stall Protection Yes
Motor Underload Protection Yes
Short Circuit Protection Yes (of the 24 V and 10 V Reference Voltages)
Surge Protection Yes (Varistor Input)
OHSPD Special Seismic Certification
Pre-Approval
Yes
Compliance UL Listed File No 508C; cUL Listed
Safety – EN 61800-5-1 (2007)
CE Mark – Johnson Controls, Inc., declares that the VSD Series II Variable
Speed Open Drives are in compliance with the essential requirements and
other relevant provisions of EMC Directive 2004/108/EC and Low Voltage
Directive 2006/95/EC.
Warranty 2 Years Standard Terms;
3 Years with Certified Startup
Reliability 500,000 Hours Mean Time Between Failures (MTBF)
Line Voltage (VAC) 230 V (208 to 240 V)
480 V (380 to 500 V)
575 V (525 to 690 V)
Weight FR4 13.2 lb (6 kg)
FR5 22 lb (10 kg)
FR6 44 lb (20 kg)
FR7 83 lb (37.5 kg)
FR8 154.3 lb (70 kg)
FR9 238 lb (108 kg)
VSD Series II Variable Speed Open Drives (Part 2 of 3)