User Guide

VSD Series II Variable Speed Open Drives Product Bulletin
21
Technical Specifications
VSD Series II Variable Speed Open Drives (Part 1 of 3)
Input Voltage (V
in
) 200 – 240 VAC, 380 – 480 VAC, -10%/+10%
Input Frequency (f
in
) 50/60 Hz (Variation Up to 47-66 Hz)
Connection to Power Once Per Minute or Less (Typical Operation)
Current Withstand Rating 100 kAIC
Output Voltage 0 to V
in
Line Voltage In
Continuous Output Current Ambient Temperature Maximum 104°F (40°C), Overload 1.1 x I
L
(1 min./10 min.)
Overload Current 110% (1 min./10 min.)
Initial Output Current 150% for 2 Seconds
Output Frequency 0 to 320 Hz
Frequency Resolution 0.01 Hz
Control Method Frequency Control (V/f) Open Loop Sensorless Vector Control
Switching Frequency 1 – 310 A
Frame 4 – 9: default 6 kHz
Frequency Reference Analog Input: Resolution 0.1% (10 bit),
Accuracy +/-1%
Panel Reference: Resolution 0.01 Hz
Field Weakening Point 8 to 320 Hz
Acceleration Time 0.1 to 3,000 s
Deceleration Time 0.1 to 3,000 s
Braking Torque DC Brake: 30% x T
n
(without Brake Option)
Ambient Operating Temperature 14 (No Frost) to 104°F (-10 to 40°C)
Storage Temperature -40 to 158°F (-40 to 70°C)
Relative Humidity 0 to 95% RH, Noncondensing, Noncorrosive,
No Dripping Water
Air Quality Chemical Vapors: IEC 60721-3-3, Unit In Operation, Class 3C2;
Mechanical Particles: IEC 60721-3-3, Unit In Operation, Class 3S2
Altitude 100% Load Capacity (No Derating) Up to 3,280 ft (1,000 m);
1% Derating for Each 328 ft (100 m) Above 3,280 ft (1,000 m);
Maximum 9,842 ft (3,000 m)
Vibration Frame 4 – 9, EN 61800-5-1, EN 60068-2-6; 5 to 150 Hz, Displacement
Amplitude 1 mm (Peak) at 5 to 15.8 Hz, Max. Acceleration Amplitude 1 G at
15.8 to 150 Hz
Shock EN 61800-5-1,EN 60068-2-27 United Parcel Service® (UPS) Drop Test (for
Applicable UPS Weights) Storage and Shipping: max. 15 G, 11 ms (in
package)
Enclosure Class NEMA Type 1/IP21 or NEMA Type 12/IP54
EMC (at default settings) Immunity: Fulfills all Electromagnetic Compatibility (EMC) Immunity
Requirements; Emissions: EN 61800-3 (2004), LEVEL H
Emissions EMC Level Dependent: +EMC 2: EN 61800-3 (2004) Category C2, Delivered
with Class C2 EMC Filtering as Default
Analog Input Voltage 0 to 10 V, R = 200 kOhms Differential Resolution 0.1%; Accuracy ±1%, Dip
Switch Selection (Voltage/Current)
Analog Input Current 0 (4) to 20 mA; R
i
- 250 Ohms Differential
Digital Inputs (6) Positive or Negative Logic; 18 to 30 VDC