Install Instructions
Table Of Contents
VG7000 Series Bronze Control Valves Installation Instructions 1
Applications
VG7000 Series Bronze Control Valves are primarily 
designed to regulate the flow of water and steam in 
response to the demand of a controller in Heating, 
Ventilating, and Air Conditioning (HVAC) systems. 
Contact the local Johnson Controls® representative for 
compatibility concerns before using VG7000 Series 
Bronze Control Valves to control the Technical 
Specifications table at the end of this document.
The installation instructions included here conform to 
the relevant and valid European Norm (EN) safety 
standards, as well as the current laws and regulations 
of the European Union. Qualified personnel are 
required for the proper application of these installation 
instructions. Qualified personnel are defined as people 
conversant with installation, mounting, commissioning, 
operation, and servicing of pneumatically and 
electrically actuated VG7000 Series Bronze Control 
Valves, through their activities and functions. Qualified 
personnel include:
• trainers and instructors with an obligation to ensure 
adherence to regional and international ordinances 
and requirements
• trainers and instructors of safety standards
• trainers and instructors of adequate facility safety 
and protective operation
• trainers and instructors of first aid
Location of Valve Data
Each VG7000 Series Bronze Control Valve shipped 
from the factory includes a brass tag chained to the 
valve bonnet that features technical data about the 
valve. The technical data on the tag includes:
•the code number of the valve
•the flow coefficient Cv of the valve
•the maximum allowable fluid temperature of the 
controlled media
•the manufacturing date code of the valve (as 
illustrated in Figure 1)
Installation
Pre-installation Details
Before installing a VG7000 Series Bronze Control 
Valve, please note the following:
• Be sure to mount the valve in an upright position, in 
a conveniently accessible location.
• Protect the electric actuator from dripping water 
that could enter the actuator housing and damage 
the mechanism or motor.
• Do not cover the actuator with insulating material.
• Allow sufficient clearance to remove the actuator 
(refer to Figure 2 and Table 1 and Table 2).
• Pipe the valve with the flow in the direction of the 
arrow on the valve body, so that the plug seats 
against the flow.
• Wire all electrically actuated valve assemblies in 
accordance with applicable electrical code 
requirements. Input lines to the actuator must be 
wired correctly for the valve to move in the proper 
direction.
IMPORTANT: The VG7000 Series Bronze Control 
Valves are intended to control saturated steam, hot 
water, and chilled water flow under normal 
equipment operating conditions. Where failure or 
malfunction of the VG7000 Series Valve could lead 
to personal injury or property damage to the 
controlled equipment or other property, additional 
precautions must be designed into the control 
system. Incorporate and maintain other devices 
such as supervisory or alarm systems or safety or 
limit controls, intended to warn of or protect against 
failure or malfunction of the VG7000 Series Valve.
Manufacturing Facility
w  wy   y
M
Week
Year
fig:mfgdtcd
Figure 1: Manufacturing Date Code
VG7000 Series Bronze Control Valves
Installation Instructions
VG7000
Part No. 14-1078-6, Rev. E
Issued June 16, 2008
Supersedes August 12, 2002