Install Instructions
Table Of Contents
Published in U.S.A. www.johnsoncontrols.com
VG7000 Series Bronze Control Valves Installation Instructions8
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2013 Johnson Controls, Inc.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Valve Fluid Operating 
Temperature Limits
Brass Trim 
Valve with 
Pneumatic 
Actuator
For V-3801-8001 and V-3000-8003 Actuators:
35 to 248°F (2 to 120°C) Water; 15 psig (103 kPa) Saturated Steam
For MP82 and V-3000-8012 Actuators:
35 to 284°F (2 to 140°C) Water; 38 psig (262 kPa) Saturated Steam
Brass Trim 
Valve with 
Electric 
Actuator
For VA-8x2x Actuators:
195°F (91°C) Maximum Water; Actuators are not rated for steam.
For VA-4233-xGx-2 Actuators:
35 to 250°F (2 to 121°C) Water; 15 psig (103 kPa) Saturated Steam
For All Other Electric Actuators:
35 to 284°F (2 to 140°C) Water; 38 psig (262 kPa) Saturated Steam
SS Trim 
Valve with 
Pneumatic 
Actuator
All Pneumatic Actuators:
35 to 338°F (2 to 170°C) Water; 100 psig (690 kPa) Saturated Steam
SS Trim 
Valve with 
Electric 
Actuator
For VA-4233-xGx-2 Actuators:
35 to 250°F (2 to 121°C) Water; 15 psig (103 kPa) Saturated Steam
For All Other Electric Actuators:
35 to 338°F (2 to 170°C) Water; 100 psig (690 kPa) Saturated Steam
Actuator Ambient Operating 
Temperature Limits
Refer to the appropriate actuator or linkage kit product bulletin. Ambient 
operating temperature or other service limitations vary by selected 
actuator.
Compliance 1/2, 3/4, and 
1 in. Valves
Pressure Equipment Directive (PED) 97/23/EC: 
Paragraph 3, Comma 3 (CE Marking not Applicable.)
1-1/4, 1-1/2, 
and 2 in. 
Valves
Pressure Equipment Directive (PED) 97/23/EC: 
Category 1, Mod. A (Subject to CE Marking)
All Valve 
Sizes
CRN: C1099.9087YTN
1. Proper water treatment is recommended; refer to VDI 2035 Guideline.
2. Rangeability is defined as the ratio of maximum flow to minimum controllable flow.
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these 
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or 
misuse of its products.
VG7000 Series Bronze Control Valves (Part 3 of 3)