Product Overview

VG1000 Series Forged Brass Ball Valves Product Bulletin42
1-1/2
(DN40)
VG1241Ex
VG1245Ex
VG1841Ex
VG1845Ex
M9106 M9000-520
M9108 M9000-516 M9000-330
VA9208 None Required
(Fluid Temperature
212°F)
M9000-341
M9000-561 (Fluid
Temperature
284°F)
2 (DN50) VG1241Fx
VG1245Fx
VG1841Fx
VG1845Fx
M9109 M9000-520
M9108 M9000-516 M9000-330
VA9208 None Required
(Fluid Temperature
212°F)
M9000-341
M9000-561 (Fluid
Temperature
284°F)
1. VA9104, M9104, M9106, and M9109 Series Actuators are non-spring return; and VA9203 and VA9208 Series Actuators are
spring return. Note: All actuators have a maximum fluid temperature limit of 212°F (100°C). Temperatures can be increased
to 284°F (140°C) or 15 psi steam with the addition of the M9000-561 thermal barrier.
2. To avoid excessive wear or drive time on the motor for VA9104, M9104, and M9109 AGx models, use a controller and/or
software that provides a timeout function to remove the signal at the end of rotation (stall). The IGx and GGx models have
an automatic shutoff to avoid excessive wear or drive time on the motor.
Table 36: Valid Ball Valve, Electric Actuator, Linkage Kit, and Weather Shield Combinations (for Assembly
in the Field) (Part 3 of 3)
Valve Size,
in. (DN)
Valve Code Numbers Actuator
Base
Number
1
Linkage Kit
Code Number
Weather
Shield
NPT End
Connection
Sweat End
Connection
Press End
Connection