Electric Non-Spring Return Valve Actuators (Continued)
Accessories (Order Separately)
Technical Specifications
Code Number Description
M9000-200 Commissioning Tool that Provides a Control Signal to Drive 24 V On/Off, Floating, Proportional, and/or Resistive Electric Actuators
M9000-341 Weather Shield Kit for VG1000 Series Ball application of VA9104, M(VA) 9203, and M(VA)9208 Series Electric Non-Spring Return
Actuators (quantity 1)
M9000-551 Mounting Hardware Replacement Kit (quantity 1)
M9000-561 Thermal Barrier Kit for M9000-551 and M9000-560 Ball Valve Linkages. Extends the VA9104, M(VA) 9203, and M(VA)9208 Series
Electric Non-Spring Return Actuators applications to include low pressure steam (quantity 1).
VA9104-xGA-2S, -3S Series Electric Non-Spring Return Valve Actuators
Power Requirements AC 24 V +25%/-20% at 50/60 Hz, 2.1 VA Supply, Class 2 or Safety Extra-Low Voltage (SELV)
Control Type VA9104-AGA-xS Floating Control without Timeout
VA9104-GGA-xS Proportional Control
VA9104-IGA-xS Floating or On/Off Control with Timeout
Control Signal VA9104-AGA-xS AC 24 V +25%/-20% at 50/60 Hz, Class 2 or SELV Without Timeout
VA9104-GGA-xS DC 0 (2) to 10 V or 0 (4) to 20 mA With Field Furnished 500 ohm Resistor
VA9104-IGA-xS AC 24 V +25%/-20% at 50/60 Hz, Class 2 or SELV With Timeout
Control Input Impedance VA9104-GGA-xS Voltage Input: 200,000 ohms
Current Input: 500 ohms With Field Furnished 500 ohm Resistor
Running Torque 35 lb
⋅in (4 N⋅m)
Travel Time 60 Seconds at 60 Hz (72 Seconds at 50 Hz) for 90° of Rotation
Rotation Range 93° ±3°, CW or CCW
Cycles 100,000 Full Stroke Cycles; 2,500,000 Repositions at Rated Running Torque
Audible Noise Rating 35 dBA Nominal at 39-13/32 in. (1 m)
Electrical Connections VA9104-xGA-2S 48 in. (1.2 m) UL 444 Type CMP Plenum Rated cable with 19 AWG (0.75 mm
2
) conductors and
0.25 in. (6 mm) ferrule ends and connector for 3/8 in. (9.5 mm) flexible metal conduit.
VA9104-xGA-3S M3 Screw Terminals (Requires a Slotted Screwdriver)
Enclosure VA9104-xGA-2S NEMA 2, IP42
VA9104-xGA-3S NEMA 1, IP40
Ambient Conditions Operating -4 to 140°F (-20 to 60°C); 90% RH Maximum, Noncondensing
Storage -20 to 150°F (-29 to 66°C); 90% RH Maximum, Noncondensing
Fluid Temperature Limits
(Actuator and Valve Assembly)
VG12x1 and VG18x1 Series 23 to 203°F (-5 to 95°C)
VG12x5 and VG18x5 Series -22 to 212°F (-30 to 100°C)
VG12x5 and VG18x5 Series
With M9000-561 Thermal
Barrier Installed
-22 to 284°F (-30 to 140°C) water; 15 psig (103 kPa) at 250°F (121°C) Saturated Steam
Compliance United States UL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1, Automatic Electrical
Controls for Household and Similar Use; and UL 60730-2-14: 2002-02, Ed. 1, Part 2 Particular
Requirements for Electric Actuators
Canada UL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA: July 2002, 3rd Ed.,
Automatic Electrical Controls for Household and Similar Use; and CSA C22.2 No. 24-93
Temperature Indicating and Regulating Equipment
Europe CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the essential
requirements and other relevant provisions of the EMC Directive 2004/108/EC and
Low Voltage Directive 2006/95/EC.
Australia and New Zealand C-Tick Mark, Australia/NZ Emissions Compliant
Shipping Weight 1.25 lb (0.55 kg)