DS-3153 High-Temperature Pneumatic Piston Damper Actuator
Description
The DS-3153 Pneumatic Actuator is a
multipurpose positioning device used primarily
for operating smoke ventilating dampers in
response to the output signals of a pneumatic
controller or electro-pneumatic transducer
during life safety applications.
The DS-3153 can be used with dampers up to
a maximum area of 16 square feet for
proportional volume control and 25 square
feet for two-position actuation, provided that
the torque requirements are compatible with
the specific application.
The DS-3153 is UL/cUL component
recognized for use on UL classified 555/555S
smoke and combination fire/smoke dampers,
which have been tested and approved to a
degradation temperature of 350
°F (176°C).
Refer to the DS-3153 Pneumatic Actuator
Product Bulletin (LIT-2681072) for important
product application information.
Features
high-temperature pilot positioner available
for additional positioning power and
sequential control
all metal bearings for high-temperature
exposure
all-aluminum housing, which is lightweight
and non-combustible
telescoping linkage for fast and flexible
installation
two-way swivel head to ensure full power
delivery
3-year warranty to provide confidence of
company standing behind product
Applications
When used with proportional control, the
damper size is limited to 16 square feet
maximum. As a two-position control, the
damper size is limited to 25 square feet.
The nominal spring range is 8 to 13 psi. The
control air pressure for normal HVAC
operation is 0 to 20 psig. The minimum control
pressure for safety damper functions is
20 psig with the maximum pressure of
30 psig. When used for both proportional and
safety applications, a separate air signal
should be provided to override normal HVAC
operation and cause safety damper functions.
Where precision sequential operation is
desired, or additional positioning power is
necessary, a pilot positioner is available.
Repair Information
If the DS-3153 Pneumatic Actuator fails to
operate within its specifications, replace the
unit. For a replacement actuator, contact the
nearest Johnson Controls® representative.
Selection Chart
Code Number Nominal Spring Range, psig (kPa)
DS-3153-1 8 to 13 (56 to 91) with Pilot Positioner and Universal
Mounting Bracket
DS-3153-2 8 to 13 (56 to 91) with Universal Mounting Bracket
DS-3153-4 8 to 13 (56 to 91) with Pilot Positioner and Auxiliary
Mounting Bracket
DS-3153-5 8 to 13 (56 to 91) with Auxiliary Mounting Bracket
Accessories
Code Number Description Shipping Weight,
lb (Kg)
D-3073-100 Rubber Boot Kit 0.2 (0.91)
D-3073-604 Ball Joint Weather Resistant 0.3 (0.11)
DMPR-KC054 Blade Arm Kit 1.0 (0.45)
DMPR-KC051 Crankarm 3/8 in. Adjustable to
2-3/4 in. Radius
0.5 (0.23)
DMPR-KC050 Crankarm 7/16 in. Adjustable to
2-3/4 in. Radius
0.5 (0.23)
DMPR-KC102 Linkage Rod 4 ft (122 cm) 2.0 (0.91)
D-3153-103 Linkage Rod Replacement 1.0 (0.45)
Code No. LIT-1921765
DS-3153 High-Temperature Pneumatic
Piston Damper Actuator
Pneumatic Damper Actuators
Technical Specifications
DS-3153 High-Temperature Pneumatic Piston Damper Actuator
Stroke 3 in. (76 mm)
Control Air Pressure 0-20 psig for HVAC
20 psig (137 kPa) minimum for safety damper functions
30 psig (205 kPa) maximum
Force at 20 psig (140kPa)
Supply
Stroke Force, lb (Newton) Torque Output at 90° Rotation
Power 105 (467) 158 lb·in (18 N·m)
Return 120 (534) 180 lb·in (20 N·m)
Air Connections Compression fitting for 1/4 in. O.D. copper tubing (furnished)
Ambient Operating Conditions -20 to 150°F (-29 to 66°C)
Effective Diaphragm Area 15 in
2
(97 cm
2
)
Materials Body - die cast aluminum; diaphragm - synthetic elastomer
Dimensions 5-1/14 in. diameter x 10 in. long
Shipping Weight, lb (Kg) DS-3153-1 10.5 (4.8) DS-3153-2 10.5 (4.8)
DS-3153-4 10.5 (4.8) DS-3153-5 8.5 (3.9)
Agency Listing UL Recognized component to 350°F (176°C) with compression fitting for copper tubing File No. R15581