D-3062 Pneumatic Piston Damper Actuator (Continued)
Pneumatic Damper Actuators
Technical Specifications
Maximum Actuator Force at 20 psig (140 kPa)
Note: Force calculated using 6.6 lb/psig available actuator force
D-3062 Pneumatic Piston Damper Actuator
Stroke 2 in. (51 mm)
Control Air Pressure 0 to 20 psig for HVAC
20 psig (137 kPa) minimum for safety damper functions
30 psig (205 kPa) maximum
Air Connections 1/8 in. NPT straight barbed fitting for 5/32 or 1/4 in. O.D. polytubing (furnished)
Compression fitting for 1/4 in. O.D. copper tubing (F-200-3, order separately)
Ambient Operating Conditions (HVAC) -20 to 150°F (-29 to 66°C)
Effective Diaphragm Area 6.6 in.
2
(43 cm
2
)
Materials Body - aluminum; diaphragm - synthetic elastomer
Dimensions 3-3/16 in. diameter x 6-13/16 in. long
Shipping Weight, lb (kg) 1.2 (0.54)
Agency Listing UL Recognized component to 250°F (121°C) with compression fitting for copper tubing File No. R15581
Nominal Spring Range, psig (kPa) Stroke Force, lb (Newton) Torque Output for 90° Rotation D-3062-Suffix
3 to 7
(21 to 49)
Power 85.8 (382) 85.8 lb·in (9.69 N·m) -1
Return 19.8 (88) 19.8 lb·in (2.24 N·m)
5 to 10
(35 to 70)
Power 66 (294) 66 lb·in (7.45 N·m) -2
Return 33 (147) 33 lb·in (3.73 N·m)
8 to 13
(56 to 91)
Power 46.2 (206) 46.2 lb·in (5.22 N·m) -3
-41
Return 52.8 (235) 52.8 lb·in (5.96 N·m)
11 to 15
(77 to 105)
Power 33 (147) 33 lb·in (3.73 N·m) -4
Return 72.6 (323) 72.6 lb·in (8.20 N·m)