Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
www.johnsoncontrols.com
V–36
M9108, M9116, M9124, and M9132 Series Electric Non-Spring-Return Actuators
(Continued)
Electric Damper Actuators
Technical Specifications
M9108, M9116, M9124, and M9132 Series Electric Non-Spring-Return Actuators
Power Requirement M9108- and M9116-AGx: AC 20 to 30 V at 50/60 Hz or DC 24 V ±10%; 6.5 VA supply minimum
All other models: AC 20 to 30 V at 50/60 Hz or DC 24 V ±10%; 7.5 VA supply minimum
Control Type AGx: on/off and floating
GGx: DC 0(2) to 10 V or DC 0(4) to 20 mA proportional
HGx: DC 0 to 10 V or DC 0 to 20 mA proportional with adjustable start and span
JGx: proportional from 100 to 10,000 ohm potentiometer controller
Input Signal AGx: V 24 AC at 50/60 Hz or DC 24 V
GGx and HGx: DC 0(2) to 10 V, DC 0(4) to 20 V, or DC 0(4) to 20 mA
JGx: potentiometer value is 100 ohms minimum to 10,000 ohms maximum
Input Signal Adjustments AGx: factory setting, terminals 1 and 2, CW rotation; terminals 1 and 3, CCW rotation
GGx and HGx (voltage input or current input):
Jumper selectable: DC 0(2) to 10 V, DC 0(4) to 20 V, or DC0(4) to 20 mA
Adjustable: zero, DC 0 to 6 V, DC 0 to 12 V, or DC 0 to 12 mA
Span, DC 2 to 10 V, DC 4 to 20 V, or DC 4 to 20 mA
Factory setting: DC 0 to 10 V, DC 0 to 20 mA, CW rotation with signal increase
GGx, HGx, and JGx: action is jumper selectable direct (CW) or reverse (CCW) with signal increase.
Input Impedance GGx and HGx: voltage input, 205,000 ohms for 0 (2) to 10 V and 410,000 ohms for 0 (4) to 20 V; current input,
500 ohms
JGx: 1.8 megohms
Feedback Signal AGD: 135 ohm feedback potentiometer
AGE: 1,000 ohm feedback potentiometer
GGx and HGx: DC 0 to 10 V or DC 2 to 10 V for 90° (10 VDC at 1 mA) corresponds to input signal span selection.
JGx: DC 0 to 10 V for 90° (10 VDC at 1 mA)
Auxiliary Switch Rating xGC: two single-pole, double-throw (SPDT) switches rated at 24 VAC 1.5 A inductive, 3.0 A resistive, 35 VA
maximum per switch, Class 2
Torque Rating M9108: 70 lb·in (8 N·m) for one unit; not intended for tandem use
M9116: 140 lb·in (16 N·m) for one unit, 280 lb·in (32 N·m) for two in tandem (-GGx, -HGx)
M9124: 210 lb·in (24 N·m) for one unit, 420 lb·in (48 N·m) for two in tandem (-AGx, -GGx, -HGx)
M9132: 280 lb·in (32 N·m) for one unit, 560 lb·in (64 N·m) for two in tandem (-AGx, -GGx)
Cycle Life M9108, M9116 and M9124 60,000 cycles at rated load
M9132 30,000 cycles at rated load
Audible Noise Rating 45 dBA at 1 m
Rotation Range 0 to 90° in 5-degree increments, mechanically limited to 93° - rotation range is adjusted by repositioning the output
hub
Rotation Time M9108: 30 seconds at 50% rated load, 25 to 50 seconds for 0 to 70 lb·in (0 to 8 N·m)
M9116: 80 seconds at 50% rated load, 70 to 115 seconds for 0 to 140 lb·in (0 to 16 N·m)
M9124: 130 seconds at 50% rated load, 115 to 175 seconds for 0 to 210 lb·in (0 to 24 N·m)
M9132: 140 seconds at 50% rated load, 115 to 205 seconds for 0 to 280 lb·in (0 to 32 N·m)
Electrical Connection M9124- and M9132-AGx: 1/4 in. spade terminals with pluggable 3-terminal blocks (see Accessories
)
All other models: screw terminals for 22 to 14 AWG; maximum of two 18, 20, or 22 AWG per terminal
Mechanical Connection 3/8 to 3/4 in. (10 to 20 mm) diameter round shaft or 3/8 to 5/8 in. (10 to 16 mm) square shaft
1 in. (25.4 mm) diameter jackshaft with M9000-154 coupler
Enclosure Rating NEMA 2, IP42
Ambient Operating Rating -4 to 122°F (-20 to 50°C); 0 to 95% RH, noncondensing
Ambient Storage Rating -40 to 186°F (-40 to 86°C); 0 to 95% RH, noncondensing
Shipping Weight 2.9 lb (1.3 kg)
Compliance United States UL 873 Listed, File E27734, CCN XAPX
Canada CSA C22.2 No. 139 Certified, File LR85083, Class 3221 02
Europe CE Mark - Johnson Controls, Inc. declares that this product is in compliance with the essential requirements and
other relevant provisions of the EMC Directive 2004/108/EC.
Electric Damper Actuators
Electric Damper Actuators
Electric Damper ActuatorsElectric Damper Actuators