Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
www.johnsoncontrols.com
V–307
P1000 Series Pressure-Independent Valves (Continued)
Pressure-Independent Valves
Technical Specifications
2 P1241F33 33 100
P1241F34 34
P1241F35 35
P1241F36 36
P1241F37 37
P1241F38 38
P1241F39 39
P1241F40 40
P1241F44 44
P1241F48 48
P1241F52 52
P1241F56 56
P1241F60 60
P1241F65 65
P1241F70 70
P1241F75 75
P1241F80 80
P1241F90 90
P1241F100 100
P1000 Series Pressure-Independent Valves (Part 1 of 2)
Service
1
Hot or Chilled Water, and 60% Glycol Solutions for HVAC Systems
Valve Fluid Temperature Limits 0 to 212°F (-18 to 100°C)
Valve Body Pressure/Temperature Rating 600 psig (4,134 kPa) - Sizes 1/2, 3/4, and 1 in.
400 psig (2,756 kPa) - Sizes 1-1/4, 1-1/2, and 2 in.
Maximum Closeoff Pressure 200 psi (1,378 kPa)
Recommended Minimum Differential Operating Pressure 5 psi (34 kPa)
Maximum Recommended Operating Pressure Drop 50 psi Maximum Differential Pressure
Flow Characteristics Equal Percentage
Flow Accuracy ±10% Combination of Manufacturing Tolerances and Pressure Variations
Valve Body Size/Flow Rate See Field Adjustable Flow Ranges and Runtime Data
.
Leakage 0.01% of Maximum Flow per ANSI/FCI 70-2, Class 4
End Connections National Pipe Thread (NPT)
Material Body Forged Brass, Nickel Plated
Ball Chrome-Plated Brass
Stem Chrome-Plated Brass
Seats Fiberglass Reinforced Teflon® Polytetrafluoroethylene (PTFE)
Characterizing Disk Tef ze l®
Packing Two Ethylene Propylene Diene Monomer (EPDM) O-Rings
Diaphragm Polyester Reinforced Silicone
Regulator Stainless Steel/Brass/Delrin
Spring Stainless Steel
Power Requirements VA2104-AGA-2 AC 24 V ±20%, 50/60 Hz, DC 24 V ±10%, 3 VA Supply Class 2
VA2104-HGA-2 AC 24 V ±20%, 50/60 Hz, DC 24 V ±10%, 4 VA Supply Class 2
VA2120-HGA-2 AC 24 V ±20%, 50/60 Hz, DC 24 V ±10%, 5 VA Supply Class 2
VA2202-HGA-2P AC 24 V ±20%, 50/60 Hz, DC 24 V ±10%, 4 VA Supply Class 2
M2204-HGA-2 AC 24 V ±20%, 50/60 Hz, DC 24 V ±10%, 5 VA Supply Class 2
M2215-HGA-2 AC 24 V ±20%, 50/60 Hz, DC 24 V ±10%, 10 VA Supply Class 2
Field Adjustable Flow Ranges and Runtime Data (Part 2 of 2)
Size, in. Valve Code Number Factory Flow Rate,
gpm
Field Adjustable Flow
Range Using
FlowSetR
Base,
gpm
Running Time (Seconds)
Without Pressure
Taps
VA2104-AGA-2 VA2104-HGA-2
VA2120-HGA-2
VA2202-HGA-2P
M2204-HGA-2
M2215-HGA-2
Threaded Ball Valves and
Actuators
Pressure-Independent
Valves
Threaded Ball Valves and
Actuators
Pressure-Independent
Valves