Brochure

Table Of Contents
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2014 Johnson Controls, Inc.
www.johnsoncontrols.com
V–293
VA-9070 Series Electric Rotary Actuators for Two-Position and Modulating
Service
Code No. LIT-1924415
Description
The VA-9070 Series Electric Rotary Actuators for Two-Position and
Modulating Service are designed for direct mounting on VF Series
Butterfly Valves. The VA-9070 is available in eight different sizes, for
two-position and modulating service on VF Series Standard-Pressure,
Standard-Temperature Butterfly Valves and VF Series High-Pressure,
High-Temperature Buttery Valves.
Refer to the VA-9070 Series Electric Rotary Actuators for Two-Position
and Modulating Service Product Bulletin (LIT-977319) for important
product application information.
Features
low-profile and lightweight design
built-in motor overload protection
pre-wired actuator switches to terminal block; field-configurable
power and input signals
patented travel limit switch cam design
external manual handwheel override
rugged, die-cast aluminum National Electrical Manufacturers'
Association (NEMA) 4, 4X, IP65 Type enclosure and captive
housing screws
valve status display
heater/thermostat
Actuator Selection for Two-Way Standard-Performance
VF Series Butterfly Valves
Valve
Size, in.
Torque
Required, lb·in
(N·m)
Actuator Code Number for
Two-Position
Service
Modulating
Service
150 or 175 psig (High) Closeoff Pressure
1
2 158 (17.9)
2
VA-9072-02 or
VA-9072-12
VA-9072-01 or
VA-9072-11
2-1/2 188 (21.2)
2
3 225 (25.4)
2
4 465 (52.5)
2
5 585 (66.1)
2
VA-9073-02 or
VA-9075-12
VA-9073-01 or
VA-9075-11
6 705 (79.7)
2
8 1,530 (172.9)
2
VA-9075-02 or
VA-9075-12
VA-9075-01 or
VA-9075-11
10 3,296 (372.4)
2
VA-9076-02 or
VA-9077-12
VA-9076-01 or
VA-9077-11
12 5,165 (583.6)
2
VA-9077-02 or
VA-9077-12
VA-9077-01 or
VA-9077-11
14 6,450 (728.8)
2
VA-9078-02 VA-9078-01
50 psig (Low) Closeoff Pressure
3
4 225 (25.4)
2
VA-9072-02 or
VA-9072-12
VA-9072-01 or
VA-9072-11
5 390 (44.1)
2
6 570 (64.4)
2
8 705 (79.7)
2
VA-9073-02 or
VA-9075-12
VA-9073-01 or
VA-9075-11
10 1,410 (159.3)
2
VA-9075-02 or
VA-9075-12
VA-9075-01 or
VA-9075-11
12 2,595 (293.2)
2
VA-9076-02 or
VA-9077-12
VA-9076-01 or
VA-9077-11
14 3,300 (372.9)
2
VA-9077-02 or
VA-9077-12
VA-9077-01 or
VA-9077-11
16 4,268 (482.2)
2
VA-9077-02 or
VA-9077-12
VA-9077-01 or
VA-9077-11
18 5,267 (595.1)
2
VA-9078-02 VA-9078-01
1. 150 psig (1,034 kPa) for 14 in. valves; 175 psig (1,207 kPa) for 2 through
12 in. valves
2. Torque values have already been adjusted for 25% safety factor on 2 through
12 in. valves, and 10% safety factor on 14 in. valves.
3. 50 psig (345 kPa) for 4 through 20 in. valves
Selection Charts
Code Numbers and Cross-Reference Data
Johnson Controls
Actuator Only
Code Number
Johnson Controls
VF Series Butterfly
Valve Assembly
Actuator Sub-Code
Bray Series Number
Electric Two-Position Models
VA-9072-02 -722 S70-005 On/Off
VA-9073-02 -723 S70-008 On/Off
VA-9074-02 -724 S70-012 On/Off
VA-9075-02 -725 S70-020 On/Off
VA-9076-02 -726 S70-030 On/Off
VA-9077-02 -727 S70-050 On/Off
VA-9078-02 -728 S70-065 On/Off
VA-9072-12 -722D4 S70-005 On/Off,
AC 24V
VA-9075-12 -725D4 S70-020 On/Off,
AC 24V
VA-9077-12 -727D4 S70-050 On/Off,
AC 24V
Electric Modulating Models
VA-9072-01 -702 S70-005 Modulating
VA-9073-01 -703 S70-008 Modulating
VA-9074-01 -704 S70-012 Modulating
VA-9075-01 -705 S70-020 Modulating
VA-9076-01 -706 S70-030 Modulating
VA-9077-01 -707 S70-050 Modulating
VA-9078-01 -708 S70-065 Modulating
VA-9072-11 -702N4 S70-005 Modulating,
AC 24V
VA-9075-11 -705N4 S70-020 Modulating,
AC 24V
VA-9077-11 -707N4 S70-050 Modulating,
AC 24V
VA-9070 Series Electric Rotary Actuator Mounted on a
VF Series Butterfly Valve
Repair Information
If the VA-9070 Series Electric Actuator fails to operate within its
specifications, replace the unit. For a replacement actuator, contact the
nearest Johnson Controls® representative.